MOUNTING THE BOILER
Due care should be taken when lifting the boilers,
with respect to their weights, see below.
W45 = 87kg
W60 = 88kg
W80 = 101kg
Lift the boiler onto the wall mounting plate as shown.
Note: It is not necessary to hold the boiler at an angle
to engage the wall mounting plate.
Using the remaining coach screw, secure the bottom
of the boiler to the wall through the attached bracket.

10 VENTILATION

The ventilation requirements of these boilers is dependant
on the type of flue system used, and their heat input. All
vents must be permanent with no means of closing, and
positioned to avoid accidental obstruction by blocking or
flooding.
W45, W60, W45P and W60P
Detail reference should be made to BS. 5440 Pt. 2. In IE
refer to the current edition of I.S. 813.
The following notes are for general guidance only:
If installed as a room sealed appliance in a room or internal
space, then no purpose provided ventilation is required.
If installed as an open flued appliance in a room or internal
space then a permanent air vent is required. The sizes
given below are for vents directly communicating with
outside air. For other situations refer to BS. 5440 Pt. 2. In IE
refer to the current edition of I.S. 813.
Boiler Size
W45 & W45P
Minimum vent free
2
area (cm
)
If installed in a compartment, then permanent air vents are
required at high and low level. These vents may
communicate direct to outside air, or to a room/internal
space. If to a room/internal space, it must itself be
adequately ventilated as above.
W45, W60, W45P and W60P
Minimum vent free
area (cm
2
)
positioned at:
W45/W45P
High Level
Low Level
12
INSTALLATION
W60 & W60P
190
265
Open-flued
To room or internal
Direct to outside air
space
W60/W60P W45/W45P W60/W60P W45/W45P W60/W60P W45/W45P W60/W60P
450
600
225
900
1200
450
W80, W80P and multiple boiler installations
Detail reference should be made to BS. 6644 for inputs
between 60kW and 2MW. In IE refer to the current edition of
I.S.820. The following notes are for general guidance only:
If ventilation is to be provided by means of permanent high
and low vents communicating direct with outside air, then
reference can be made to the sizes below. For other
ventilation options refer to BS. 6644. In IE refer to the current
edition of I.S.820.
W80 and W80P
Total input
rating of boilers
Up to 2 MW
HIGH LEVEL
Up to 2 MW
LOW LEVEL
Roomsealed
To room or internal
space
300
450
600
600
450
600
Position
Air vent areas (air
vents
direct from outside)
2
270cm
plus
2
2.25cm
per kW
in excess of 60 kW
total rated input
540cm
2
plus
4.5 cm
2
per kW
in excess of 60 kW
total rated input
Direct to outside air
225
300
225
300
-
Installation & Servicing