50 MAINS VOLTAGE CH AND DHW CONTROLS WITH DHW VALVE OUTPUT
Note.
This system will provide heating to one zone only at a time with
DHW priority. To heat more than one zone simultaneously, use
zone thermostat to energise individual zone valves with all
calls for CH applying live to terminal 5 and a call for DHW
applying live to terminal 7.
PUSH
ima5455
Alternatives: Try our programmable room thermostat, outside sensor and tank sensor kit for enhanced user comfort. Full
instructions provided with kits.
-
Installation & Servicing
INSTALLATION
Programmer Room stat
CYLINDER
ROOM
(MAXIMUM LOAD 1 AMP)
CONNECT VIA A RELAY
FOR GREATER CURRENTS)
MOTORISED POSITIONAL VALVE
(NOT MID POSITION VALVE)
If all zones are fitted with individual zone valves a hydraulic
bypass will be required to allow pump overrun. See page 6
for details.
Motorised
valve
sys
Parameter modifications see Frames
38, 39 and 40.
SYSTEM
PUMP
Parameter 35 = 03 If a live output is
required from terminal 12 for
positioning of the valve to satisfy CH
demand.
Parameter 35 = 23 If a live output is
required from terminal 12 for
positioning of the valve to satisfy DHW
demand.
Cylinder
thermostat
37