Toshiba HWS-802XWHM3-E Service Manual page 94

Air to water heat pump
Hide thumbs Also See for HWS-802XWHM3-E:
Table of Contents

Advertisement

Outdoor LED
Check code
indication
[L29]
<Indication 1> <Indication 2>
<Indication 1> <Indication 2>
<Indication 1> <Indication 2>
<Indication 1> <Indication 2>
<Indication 1> <Indication 2>
<Indication 1> <Indication 2>
<Indication 1> <Indication 2>
(No specific description indicates outdoor unit parts.)
* Any of the following abnormality may occur.
Seeing the LED on the outdoor board can determine which abnormality occurs.
Communication failure between MCUs, Heat sink temperature sensor (TH) failure, EEPROM
failure, Model not specified, Heat sink overheat failure, gas leakage detection, 4-way valve
invert failure
[Communication failure between MCUs]
Check outdoor control board
If defective, replace it
[Heat sink temperature sensor (TH) failure] → See [F13] details
[EEPROM failure] → See [F31] details
[Model not set] → See [L10] details
[Heat sink overheat failure] → See [P07] details
[Gas leakage failure] → See [P15] details
[4-way valve invert failure] → See [P19] details
93