Cooling Operation - Toshiba HWS-802XWHM3-E Service Manual

Air to water heat pump
Hide thumbs Also See for HWS-802XWHM3-E:
Table of Contents

Advertisement

Item
8-1.

4) Cooling operation

Basic
Operation
button set to "ON"
Operation instruction
signal transmit
Outdoor unit
NOTE:
No coding mode in default setting. When use the cooling mode, please change the
FC02 to "0".
Related FC
FC No.
02
Cooling mode availability
Operation flow and applicable data, etc.
ZONE1, 2
Cooling temperature: 10 °C to 25 °C
Circulation pump "ON/OFF" control
Hydro unit
Water 3-way valve control
control
Water 2-way valve control
Number of compressor revolutions control
Number of outdoor fan motor revolutions control
Pulse motor valve control
control
4-way valve control
Setting item
Default
Setting available range
1: No
0: Yes
38
Operation description
1. Purpose
Cooling
2. Details
This section performs
cooling operation
according to cooling
conditions specified for
the steps in the left.
3. Operations
1) Set the [ZONE1, 2]
remote controller
button to "ON".
2) The hydro unit
controller starts to
transmit a cooling
operation signal to the
outdoor unit control
unit.
3) The hydro unit
controller performs the
operation controls
shown in the left while
also controlling the
circulation pump, water
2-way valve, and water
3-way valve.
4) The outdoor unit
controls the
compressor, outdoor
fan motor, pulse motor
valve, and 4-way valve
based on the operation
signals transmitted by
the hydro unit.

Hide quick links: