Toshiba HWS-802XWHM3-E Service Manual page 150

Air to water heat pump
Hide thumbs Also See for HWS-802XWHM3-E:
Table of Contents

Advertisement

Exchange parts
No.
name
4
Electric parts
replacement
Work procedure
2. Reactor
1) Perform the step 1-1.
2) Remove the reactor lead connected to the control
board.
CN05 White, CN06 White
3) Cut the binding tie that binds the compressor leads
and fan motor leads.
4) Remove the reactor.
(Truss B tight screw Ø4 × 6, 2 screw)
5) Attach a new reactor.
Note)
Be sure to bind the removed binding tie by using
the commercially available binding tie.
Make sure that the fan motor lead and the reactor
body do not contact each other.
Binding tie
(Compressor lead,
Reactor lead)
Control board
Reactor lead
Binding tie
(Compressor lead,
Reactor lead)
Binding tie
(Fan motor lead,
Reactor lead)
149
Remarks
Reactor lead
Reactor body
Fan motor lead