Delta 21UT024C24 Instruction Manual page 10

Vogue ultra universal 21ut series
Table of Contents

Advertisement

Floor Ceiling Air-Conditioning Unit
Outdoor Units
31VA024C24
31VA036C24
31VA048C24
31VA060C24
"*" the fuse is located on the main board.
Notes:
Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units
① .
(Both indoor unit and outdoor unit).The appliance must be positioned so that the plug is
accessible.
The specifications of the breaker and power cable listed in the table above are determined
② .
based on the maximum power (maximum amps) of the unit.
The specifications of the power cable listed in the table above are applied to the conduit-
③ .
guarded multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and
a PVC cable jacket) used at 40°С and resistible to 90°С(see IEC 60364-5-52). If the working
condition changes, they should be modified according to the related national standard.
The specifications of the breaker listed in the table above are applied to the breaker with
④ .
the working temperature at 40°С. If the working condition changes, they should be modified
according to the related national standard.
Table 4
Power Supply
Fuse Capacity
V/Ph/Hz
220/230/1/60
220/230/1/60
220/230/1/60
220/230/1/60
6
Breaker
Capacity
A
A
24.83
20
41.93
40
51.88
50
65.83
60
Min. Power
Supply Cord
2
mm
2.10
5.30
8.40
8.40