Page 1
Specification and Manual Customer: Description: Air Conditioner for Equipment (Through Wall Mounting) Customer Part No.: Rev.: Delta Model No.: HEC0700BFB Rev.: Sample Date Code: Sample Issue Date: SEP.15 2020 Please send one copy of this specification back after you signed approval for production pre-arrangement...
The document is the exclusive property of Delta Electronics, Inc. it should not be distributed, reproduced, or any other format without prior permission of Delta.
Page 4
Part no.: Delta model no.: HEC0700BFB Warning: Installation work and electrical wiring should be done only by qualified personnel in accordance with all applicable codes, standards and national wiring regulations. Use this unit only in the manner intended by the manufacturer. If you have questions, please contact the manufacturer.
Page 5
Part no.: Delta model no.: HEC0700BFB Caution : Install the air conditioner on a wall or door strong enough to withstand the weight of the unit. Do not block the air inlets or exits. Do not install the air conditioner at any place where there is a danger or flammable gas leakage.
Page 6
Customer : Description : Air conditioner for Equipment with 700 W Rated Cooling Capacity (Through Wall Mounting) Customer P/N : Rev. : Delta model no. : HEC0700BFB Rev. : 03 Sample revision. : Date Code : Sample issue date :...
1. Product Instruction 1-1. General Description HEC0700BFB is a AC air conditioner with 230VAC power input, it is designed for IP55 sealed outdoor telecom cabinet to provide stable and optimum internal conditions for equipment and avoid hotspot inside the cabinet.
Page 8
Part no.: Delta model no.: HEC0700BFB Rated External Airflow (L35/L35) /h (CFM) 150 (90) Power & Range Input Voltage VAC/Phase/Frequency 230 / 1 / 50 or 60 Input Voltage Range 196~264 Locked Rotor Current (50/60Hz) 5 / 4.6 Alarm Dry Contact Output...
Part no.: Delta model no.: HEC0700BFB 1-5. Configuration & Maintenance Make sure the air conditioner surface sealed with mounting flange to avoid water penetrates into shelter through mounting interface. It is suggested to use gaskets sticking on the mounting flange and seal the gap between flange and cabinet with silicone gel during installation.
Part no.: Delta model no.: HEC0700BFB Do not wipe the product with organic solvent, volatile substances like toluene or gasoline, it will destroy the powder-coated surface. Turn off the power before maintaining. Please turn off power and remove dry contact connector while non-operating for a long time.
Part no.: Delta model no.: HEC0700BFB • C: Press Buttons: ↑: UP or increase ↓: DOWN or decrease SET: Parametric setup 3. Environmental Condition Operating Temperature -10 °C ~ +55 °C (+14 °F ~ +131 °F) ...
Part no.: Delta model no.: HEC0700BFB 7-2 System Default Setup 7-3 Self-Test (Operating Procedure) Press the SET button into parametric setup mode. Press UP button to choose CLR and then press SET button to execute auto self-test. If the system gets into self-test mode and LED will flash in green.
Part no.: Delta model no.: HEC0700BFB temperature is still high, system. 2. Ensure the air conditioner no obvious cooling 2. The ambient temperature is operates in correct effect. too high. temperature range. 3. Low efficiency of the 3. Clean the condenser.
Part no.: Delta model no.: HEC0700BFB 9. Reclaim At the end of the unit working life, the produce must not be disposed of as urban waste. It must be taken to a special local authority differentiated waste collection center or to a dealer providing this service.