INSTRUCTION MANUAL
VRF STANDARD FOUR-WAY CASSETTE
INDOOR UNITS
80CS SERIES
WARNING!
Read and follow all safety precautions in
Instruction Manual - improper use can cause
serious injury.
www.delta-dct.com

Advertisement

Table of Contents
loading

Summary of Contents for Delta 80CS048J24

  • Page 1 VRF STANDARD FOUR-WAY CASSETTE INDOOR UNITS 80CS SERIES INSTRUCTION MANUAL WARNING! Read and follow all safety precautions in Instruction Manual - improper use can cause serious injury. www.delta-dct.com...
  • Page 2 USER NOTICES When operating, the entire capacity of the cooperating indoor units should be no larger than that of the outdoor unit; otherwise, it would cause the shortage of cooling (heating) capacity. A breaker (or fuse) needs to be installed in every indoor unit, its capacity should accord with the indoor unit’s electrical parameter and it is capable of preventing short circuits and abnormal overload.
  • Page 3: Table Of Contents

    CONTENTS 1 Safety Information ...................1 2 Installation of the Cassette Type Indoor Unit ...........2 2.1 Schematic Diagram of Installation Spaces ..........2 2.2 Selection of the Installation Location of the Indoor Unit ......2 2.3 Important Notices ..................3 2.4 Dimension of the Ceiling Opening and Location of the Hoisting Screw (M10) ... 3 2.5 Main body for Hoisting the Air Conditioner ..........
  • Page 4: Safety Information

    1 Safety Information (1). Please read this manual carefully before using this unit, and operate it correctly according to the guide in this manual. (2). Please take special note of the meaning of two marks below: Warning! This mark means that it may cause casualty or badly hurt if the operation is incorrect.
  • Page 5: Installation Of The Cassette Type Indoor Unit

    2 Installation of the Cassette Type Indoor Unit 2.1 Schematic Diagram of Installation Spaces Wall surface Wall Wall surface surface unit:mm Ground surface Fig. 1 2.2 Selection of the Installation Location of the Indoor Unit (1). Obstruct should be put away from the intake or outlet vent of the indoor unit so that the (2).
  • Page 6: Important Notices

    Please contact the local DELTA nominated service center before installation. Any malfunction caused by the unit that is installed not by DELTA nominated service center would not be dealt with on time owing to inconvenience of the business contact.
  • Page 7: Main Body For Hoisting The Air Conditioner

    2.5 Main body for Hoisting the Air Conditioner (1). Primary Step for Installing the Indoor Unit When attaching the hoisting stand on the hoisting screw, do use nuts and gaskets individually prevent the gasket from breaking off. (2). Use of the Installation Reference Cardboard Please refer to the reference cardboard about the dimensions of the ceiling opening.
  • Page 8: Drainage Hose

    Smear freeze motoroil here Median sponge (attachment) (entwine the wiring interface with seal mat) Torque wrenc h Thread fasten(x4) Heat preservation sheath of liquid inlet Spanner tube (attachment) (for liquid tube) Heat preservation sheath of gas collection Wiring interface tube (attachment)(for Gas collection tube gas tube) Flare nut...
  • Page 9: Drain Raising Pipe

    The slant gradient of the attached drain hose should be within 75mm so that the drain hole won’t have to endure the unnecessary outside force. Please install the drain hose according to the following process if several drain hoses join together.
  • Page 10: Electrical Wiring

    Model Power Supply Capacity (A) of Ground Wire (mm of Power Cord (mm 80CS010J24 208-230V ~60Hz 80CS013J24 208-230V ~60Hz 80CS016J24 208-230V ~60Hz 80CS020J24 208-230V ~60Hz 80CS025J24 208-230V ~60Hz 80CS032J24 208-230V ~60Hz 80CS040J24 208-230V ~60Hz 80CS044J24 208-230V ~60Hz 80CS048J24 208-230V ~60Hz...
  • Page 11: Function Description Of Functional Dip Switch S7

    Notes: The size of circuit breaker and power cord in above sheet is selected based on the max power (max current) of unit. Above selection requirements of power cord size: Power cord size is based on multicore copper core cable with operation temperature of 90°C when laying on wire groove at 40°C ambient temperature (IEC 60364-5-523).
  • Page 12 Hook Latch Piping positio n Swing flap motor Sealing material Indoor unit Ceiling 5mm to 8mm Air outlet vent Decoration panel Fig. 4 Note! Improper screwing of the screws may cause the troubles shown in Fig. 5. Air leak Air leak from ceiling Water condensatation, water drop Fig.
  • Page 13 At body At pane At body At pane Fig. 7...
  • Page 14: Structure And Part Name Of The Cassette Type Indoor Unit

    Air inlet grille 80CS010J24 80CS013J24 80CS016J24 80CS020J24 80CS025J24 80CS032J24 80CS040J24 80CS044J24 80CS048J24 4 Working Temperature Range Working Temperature Range Indoor side state Outdoor side state Dry bulb temp.°C Wet bulb temp. °C Dry bulb temp. °C Wet bulb temp.°C Rated cooling Max.
  • Page 15: Wired Controller And Wireless Controller

    5 Wired Controller and Wireless Controller 5.1 Wired Controller MODE ROOM TEMP SPEED AUTO SET TEMP SWING SWING HOUR MELT TIMER ON/OFF Fig. 8 Every Part of the Wired Remote Controller Operating mode display (Cool, Dry, Fan, Heat) On/Off button Sleep mode display Timer button Environmental temp.
  • Page 16 displayed on LCD no matter the unit is turned on or off. At this time, as shown in Fig. 3 there is no graticule displayed on LCD, which means that the air conditioner is turned off. Timer setting (Fig. 10 ): Press TIMER under the OFF state to set the ON time and press TIMER under the ON state to set the OFF time.
  • Page 17 within 2 hours. Then the unit will run at this set temperature. There is no SLEEP mode under the FAN mode. Note: The SLEEP button is not available for the wired remote controller. If required, this function should be performed through the wireless remote controller. Fig.
  • Page 18 ROOM TEMP SWING Fig. 13 Temperature Adjustment (Fig. 14) (Every press of this button will increase or decrease the temperature by 1°C.) Temperature adjustment ranges 16°C~30°C under any running mode. SWING Fig. 14 Setting of the Running Mode (Fig. 15)
  • Page 19 SWING Fig. 15 Every press of the Mode button will change the running mode according to the following order: Under the COOL mode, the display of the COOL icon will on. The set temperature should be lower than the present room temp. If not, the air conditioner would not perform cooling. Under the DRY mode, the display of the DRY icon will on.
  • Page 20 the outdoor unit and fan will stop under the COOL, DRY and HEAT mode, but the LCD display will not be affected. When some error is displayed on the controller, please turn off the unit to stop and has it repaired by the specialized personnel.
  • Page 21: Wireless Controller

    5.2 Wireless Controller CAUTION! Make sure there is no obstruction between the wireless controller and the signal receiver. The signal receiving distance of the wireless controller can be up to 10 metes. Never drop or throw the wireless controller randomly. Never expose the wireless controller under the sunlight directly or where it is very hot.
  • Page 22 Pressing X-FAN button in COOL or DRY mode, the icon “ ” is displayed and the indoor fan will continue operation for 10 minutes in order to dry the indoor X-FAN button unit even though you have turned off the unit. After energization, X-FAN OFF is defaulted.
  • Page 23 By pessing this button it is available to go to the TIMER OFF settting state with TIMER OFF the same setting method as that of the TIMER ON, in which case the TIMER button OFF symbol will blink. By pressing this button it is allowed to select the temperature option, the indoor setting temperature or the indoor ambient temperature.
  • Page 24: Replacement Of Batteries

    down. After releasing the button, the louvre will stop swinging and keep the current status. When the louvre starts swinging, by pressing the Swing Up/Down button 2 seconds later, the louvre will stop swinging directly; while, by pressing the Swing Up/Down button within 2 seconds, the louver will keep swinging.
  • Page 25: Operation Method In Case Of Emergency

    6 Operation Method In Case of Emergency When the wireless remote controller is lost or damaged, the following method could be adopted to control the cassette type indoor unit: When the unit is turned off, press the AUTO button on corner outer cover II, then the unit begin operate in cooling with the fan run in high speed.
  • Page 26: Troubleshooting

    7 Troubleshooting Warning! power switch immediately and then contact the service center. If the abnormal state continues, the the conditioner. Phenomena Causes Remedial Measures The fuse or breaker is broken Change the fuse or close the breaker Power failure Restart when power supply is restored Power supply does not connect through Connect the power well Air conditioner...
  • Page 27 “Malfunction” Causes The air The overload protection switch acts and the conditioner Start the unit soon after it is turned off restart is 3 minutes delayed. doesn’t run Mist is blown The high humidity air in the room is cooled out from the air When cooling rapidly...
  • Page 28: Maintenance

    8 Maintenance When the air conditioner is not to be used for long time, please cut off the main power supply to the air conditioner. Warning! Do turn off the unit and cut off the main power supply when cleaning the air conditioner, otherwise electric shock or harm may happen.
  • Page 29 Capable of adsorbing CO, CO , benzene, aldehydes and odor of gasoline etc.. bacteria, and virus. the nearest DELTA service center. Cleaning the Outlet Vent and the Surface Panel Clean the surface panel by soft dry cloth or wet cloth with neutral cleaner.
  • Page 30 Model and Technical Specifications ● Specifications of cassette type indoor unit Model 80CS010J24 80CS013J24 Function Cooling and Heating Cooling and Heating Cooling Capacity 2.8 / 9,600 3.6 / 12,300 (kw/Btu/h) Heating Capacity 3.2 / 10,900 4.0 / 13,600 (kw/Btu/h) Air Flow Rate (CFM)...
  • Page 31 Main body:840×840×320 mm, 33”×33”×12-5/8” (W×D×H) Panel:950×950×60 mm, 37-3/8”×37-3/8”×2-3/8” (Main body/Panel) Package Dimensions Main body:960×960×394 mm, 37-3/4”×37-3/4”×15-1/2” (W×D×H) Panel:1025×1040×115 mm, 40-3/8”×40-7/8”×4-1/2” (Main body/Panel) Model 80CS048J24 Function Cooling and Heating Cooling Capacity 14.0 / 47,800 (kw/Btu/h) Heating Capacity 14.5 / 49,500 (kw/Btu/h) Air Flow Rate 1100 (CFM)...
  • Page 32 Thank you for Choosing airconditioners Perfectly engineered for your comfort. www.delta-dct.com...