Air Conditioner for Equipment Description : Customer Part No. : Rev.: HEC2010FFA Delta Model No. : Rev : Sample Date Code: Sample Issue Date : JUNE.17 2020 Please send one copy of this specification back after you signed approval for production pre-arrangement...
Delta model no. : HEC2010FFA Description This document is an installation and the characteristics of Delta HEC series. Before installing the unit, please read this manual thoroughly, and following the instructions contained in it. The document is the exclusive property of Delta Electronics, Inc. it should not be distributed, reproduced, or any other format without prior permission of Delta.
Page 4
Part no. : Delta model no. : HEC2010FFA Warning: Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes, standards and national wiring regulations. Use this unit only in the manner intended by the manufacturer. If you have questions, please contact the manufacturer.
Page 5
Part no. : Delta model no. : HEC2010FFA To avoid injury, do not touch the air inlet or aluminum fins of unit. Watch your steps at the time of fin cleaning or air conditioner inspection. Do not topple the air conditioner while moving or storage.
Page 6
Part no. : Delta model no. : HEC2010FFA Specification for Approval Customer : Description : Air conditioner for Equipment with 2000 W or 100W/K Rated Cooling Capacity Customer P/N : Rev. : Delta model no. : HEC2010FFA Rev. : 07 Sample revision.
Product Instruction 1-1. General Description HEC2010FFA is a hybrid air conditioner with 48VDC & 230 VAC power input, it is designed for IP55 sealed outdoor telecom cabinet to provide stable and optimum internal conditions for equipment and avoid hotspot inside the cabinet.
Page 8
Part no. : Delta model no. : HEC2010FFA Cooling DC Current at L35/L35 Rated Internal Airflow (L35/L35) /h (CFM) 950 (560) Rated External Airflow (L35/L35) /h (CFM) 600 (354) Heating Capacity 1000 Power & Range Input Voltage (Control and Fan)
Part no. : Delta model no. : HEC2010FFA 1-5. Configuration & Maintenance Make sure the air conditioner surface sealed with mounting flange to avoid water penetrates into shelter through mounting interface. It is suggested to use gaskets sticking on the mounting flange and seal the gap between flange and cabinet with silicone gel during installation.
Part no. : Delta model no. : HEC2010FFA If any abnormal acoustic noise from air conditioner happened, please turn off the product and contact with customer services. The refrigerant is environmental friendly product of R134a. Little refrigerant leakage (< 5 g/ year) is allowed for application.
Part no. : Delta model no. : HEC2010FFA Panel operation • 7-Segment Display It will show the temperature inside the cabinet and system parametric setup. • : LED indicator: Power: When the system power on and the LED will light in green.
Part no. : Delta model no. : HEC2010FFA 0: Disable d1.07 External fan enable set 1: Enable (Default) : 0 0: normal Open ,abnormal Close d1.08 Dry contact set 1: normal Close ,abnormal Open (Default) : 1 0: (Not Reset) d1.09...
Page 16
Part no. : Delta model no. : HEC2010FFA 2-4. Alarm Logs & Fault Processing Alarm Items Type of alarm Alarm code Evaporator low temperature alarm E 2.1 Cabinet high temperature alarm E 2.2 Temperature protection alarm System high pressure alarm E 2.4...
Page 17
Part no. : Delta model no. : HEC2010FFA DC input under voltage alarm E5.6 EEPROM abnormal alarm E 6.1 System exception Compressor failure alarm E 6.2 Heater failure alarm E 6.3 Fault Analysis and Processing Fault State Analysis of the Reasons Solutions •...
Part no. : Delta model no. : HEC2010FFA • Re-set the target • The inside temperature is temperature according to the The air conditioner lower than the target system requirement. stop operating, and temperature. there is no alarm • Please contact Delta or signal.
Part no. : Delta model no. : HEC2010FFA 5. Safety Certification 6. Accessory Power Cable Description Cable wire size PIN1 (16AWG) (18AWG) (18AWG) -48VDC (18AWG) PIN6 (18AWG) 7. Installation Notice Check the surrounding obstacles to make sure the product get enough space for air circulate.
Part no. : Delta model no. : HEC2010FFA 8. Reclaim At the end of the unit working life, the produce must not be disposed of as urban waste. It must be taken to a special local authority differentiated waste collection center or to a dealer providing this service.
Page 21
Part no. : Delta model no. : HEC2010FFA 9. Versions REV. Description Owner Date Issue SPEC 2018.10.23 Modify air flow 2018.11.22 Modify SPEC table 2018.11.29 Modify cable dimension 2018.11.29 Issue SPEC 2018.12.07 Issue SPEC 2018.12.10 Modify alarm code Allen 2018.12.17 Delete warranty and safety description 2020.06 17...