Specifications - Toshiba RAV-SM562XT-E Owner's Manual

Hide thumbs Also See for RAV-SM562XT-E:
Table of Contents

Advertisement

Available languages

Available languages

SPECIFICATIONS

Type
Model
Power supply
Cooling capacity (kW)
Heating capacity (kW)
Cooling Amps
(A)
Cooling Watts
(W)
Heating Amps
(A)
Heating Watts
(W)
Width
Dimension
Height
Depth
Net weight
• The specifications may be subject to change without notice for purpose of improvement.
The specified air-conditioning capabilities are based on the data determined under the following conditions:
For cooling
For heating
Indoor Unit
RAV-SM562XT-E
50Hz, 220-240 V~
CAPA.
CAPA.
AMP.
0.52
WATT.
110
AMP.
0.52
WATT.
110
(mm)
1093
(mm)
633
(mm)
208
(kg)
23
Air-inlet temperature °C
Indoor coil assembly
Dry bulb
Wet bulb
27
19
Air-inlet temperature °C
Indoor coil assembly
Dry bulb
Wet bulb
20
Reverse cycle, Under Ceiling/Console Type
Outdoor Unit
RAV-SM562AT-E
5.0 (1.5 ~ 5.6)
5.6 (1.5 ~ 6.3)
8.43 – 7.68
1760
7.61 – 6.94
1590
780
0
55
290
38
Outdoor coil assembly
Dry bulb
35
Outdoor coil assembly
Dry bulb
7
22
Indoor Unit
Outdoor Unit
RAV-SM802XT-E
RAV-SM802AT-E
50Hz, 220-240 V~
6.7 (1.5 ~ 8.0)
8.0 (1.5 ~ 9.0)
0.52
12.63 – 11.54
110
0.52
12.39 – 11.32
110
1093
633
208
23
Wet bulb
24
Wet bulb
6
2610
2560
900
780
550
42

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm562at-eRav-sm802at-eRav-sm802xt-e

Table of Contents