Hide thumbs Also See for RAV-SM562AT-E:

Advertisement

AIR CONDITIONER
CLIMATISEUR
KLIMAGERÄT
CONDIZIONATORE D'ARIA
AIRE ACONDICIONADO
AR CONDICIONADO
AIRCONDITIONER
ÊËÉÌÁÔÉÓÔÉÊÏ
Heat Pump Model
Modèle à thermopompe
Geräte mit Heizung
Modello con pompa di riscaldamento
Modelo con bomba de calor
Modelo de bomba térmica
Model met warmtepomp
ÌïíôÝëï ìå Áíôëßá Èåñìüôçôáò
RAV-SM562AT-E
RAV-SM802AT-E
Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the outdoor unit.
• For installation of the indoor unit, follow the Installation Manual attached to the indoor unit.
Veuillez lire attentivement ce Manuel d'installation avant d'installer le climatiseur.
• Ce manuel décrit la procédure d'installation de l'unité extérieure.
• Pour installer l'unité intérieure, reportez-vous au Manuel d'installation fourni avec l'unité intérieure.
Bitte lesen Sie dieses Handbuch sorgfältig, bevor Sie mit der Installation des
Klimagerätes beginnen.
• In diesem Handbuch wird die Installation der Außeneinheit beschrieben.
• Um die Raumeinheit zu installieren, folgen Sie den Anweisungen in dem Handbuch, das der Raumeinheit beiliegt.
Prima di installare il condizionatore d'aria, leggere con attenzione questo manuale d'installazione.
• Questo manuale descrive il metodo d'installazione dell'unità esterna.
• Per l'installazione dell'unità interna, fare riferimento al manuale d'installazione fornito insieme all'unità interna.
Lea atentamente este Manual de instalación antes de proceder a la instalación del aparato de aire acondicionado.
• Este manual describe el método de instalación de la unidad exterior.
• Para la instalación de la unidad interior, consulte el Manual de instalación que acompaña a la unidad interior.
Leia atentamente o presente Manual de Instalação antes de instalar o Ar Condicionado.
• O presente manual descreve o método de instalar a unidade exterior.
• Para a instalação de uma unidade interior, siga o Manual de Instalação que acompanha a unidade interior.
Lees deze installatiehandleiding zorgvuldig door voordat u de airconditioner gaat installeren.
• Deze installatiemethode beschrijft de installatiemethode van de buitenunit.
• Zie voor de installatie van de binnenunit, de installatiehandleiding bij de binnenunit.
Ðáñáêáëþ äéáâÜóôå ðñïóå÷ôéêÜ ôï Åã÷åéñßäéï ÅãêáôÜóôáóçò ðñéí áðü ôçí åãêáôÜóôáóç ôïõ
Êëéìáôéóôéêïý.
• Ôï ðáñüí Åã÷åéñßäéï ðåñéãñÜöåé ôç ìÝèïäï åãêáôÜóôáóçò ôçò åîùôåñéêÞ ìïíÜäáò.
• Ãéá ôçí åãêáôÜóôáóç ôçò åóùôåñéêÞò ìïíÜäáò, áêïëïõèÞóôå ôï Åã÷åéñßäéï ÅãêáôÜóôáóçò ðïõ óõíïäåýåé
ôçí åóùôåñéêÞò ìïíÜäá.
OUTDOOR UNIT INSTALLATION MANUAL
(SPLIT TYPE)
(TYPE SPLIT)
(SPLIT-TYP)
(TIPO SPLIT)
(TIPO SPLIT)
(GESPLITST TYPE)
(ÔÕÐÏÓ SPLIT)
MANUEL D’INSTALLATION DE L’UNITE EXTERIEURE
INSTALLATIONSHANDBUCH AUSSENEINHEIT
MANUALE D’INSTALLAZIONE DELL’UNITÀ ESTERNA
MANUAL DE INSTALACIÓN DE LA UNIDAD EXTERIOR
MANUAL DE INSTALAÇÃO DA UNIDADE EXTERIOR
INSTALLATIEHANDLEIDING VOOR DE BUITENUNIT
ÅÃ×ÅÉÑÉÄÉÏ ÅÃÊÁÔÁÓÔÁÓÇÓ ÅÎÙÔÅÑÉÊÇÓ ÌÏÍÁÄÁÓ
(TIPO SPLIT)

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-SM562AT-E

  • Page 1 Modelo con bomba de calor Modelo de bomba térmica Model met warmtepomp ÌïíôÝëï ìå Áíôëßá Èåñìüôçôáò RAV-SM562AT-E RAV-SM802AT-E Please read this Installation Manual carefully before installing the Air Conditioner. • This Manual describes the installation method of the outdoor unit.
  • Page 2 ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refriger- ant R22 in order to prevent destruction of the ozone layer. UTILISATION DU NOUVEAU REFRIGERANT Ce climatiseur est d’un type inédit qui utilise le nouveau réfrigérant HFC (R410A) au lieu du réfrigérant traditionnel R22, afin d’éviter la destruction de la couche d’ozone.
  • Page 3: Table Of Contents

    CONTENTS PRECAUTIONS FOR SAFETY ........1 EVACUATING ............... 8 ACCESSORY AND REFRIGERANT ......2 ELECTRICAL WORK ..........10 SELECTION OF INSTALLATION ........ 3 FINAL INSTALLATION CHECKS ......11 REFRIGERANT PIPING ..........6 APPLICABLE CONTROL OF OUTDOOR UNIT ..12 SOMMAIRE MESURES DE SECURITE ........
  • Page 4: Precautions For Safety

    PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. • After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
  • Page 5: Accessory And Refrigerant

    • When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level. • Install the air conditioner securely in a location where the base can sustain the weight adequately. •...
  • Page 6: Selection Of Installation

    SELECTION OF INSTALLATION CAUTION When using an air conditioner under low outside temperature condition (Outside temp.:–5°C or lower) with COOL mode, prepare a duct or wind shield so that it is not affected by the wind. <Example> Suction hood (Side) Discharge hood Suction hood (Rear side)
  • Page 7: Installation Place

    Installation Place Necessary Space for Installation • A place which provides a specified space around Obstacle at rear side the outdoor unit. <Upper side is free> • A place where the operation noise and discharged air are not given to your neighbors. 1.
  • Page 8 SELECTION OF INSTALLATION <Obstacle also at the upper side> Installation of Outdoor Unit • Before installation, check strength and horizontality of the base so that abnormal sound does not 1000 generate. or more • According to the following base diagram, fix the base firmly with the anchor bolts.
  • Page 9: Refrigerant Piping

    Optional Installation Parts (Local Procure) Refrigerant Piping Connection <Piping connection> Parts name Q’ty Refrigerant piping Capacity Liquid side Gas side Liquid side : Ø6.4 mm or Ø9.5 mm Each one rank Outer Outer Gas side : Ø12.7 mm or Ø15.9 mm Thickness Thickness RAV-...
  • Page 10 REFRIGERANT PIPING REQUIREMENT Tightening of Connecting Part 1. Do not put the spanner on the cap. The valve (Unit: N•m) may be broken. Outer diam. of copper pipe Tightening torque 2. If applying excessive torque, the nut may be 6.4 mm (diam.) 14 to 18 (1.4 to 1.8 kgf•m) broken according to some installation condi- tions.
  • Page 11: Evacuating

    EVACUATING Air Purge This air conditioner can be installed up to the connecting pipe length and height difference in the following table. Height difference (m) Max. connecting Hexagonal Capacity rank pipe length (m) wrench size Outdoor unit at upper side Outdoor unit at lower side SM56 type 4 mm...
  • Page 12 EVACUATING Compound pressure gauge Pressure gauge –101kPa (–76cmHg) Manifold valve Handle Lo Handle Hi Flare nut Valve unit (Keep fully closed) Charge hose Stopper Charge hose (For R410A only) (For R410A only) Charge cap Vacuum pump adapter for counter-flow prevention (For R410A only) Charge port Valve rod...
  • Page 13: Electrical Work

    ELECTRICAL WORK For the air conditioner that has no power cable, How to wire connect a power cable as mentioned below. 1. Connect the connecting cable to the terminal as identified with their respective numbers on the Model RAV-SM56, RAV-SM80 terminal block of indoor and outdoor unit.
  • Page 14: Final Installation Checks

    FINAL INSTALLATION CHECKS Check and Test Operation Valve cover For R410A, use the leak detector exclusively manufactured for HFC refrigerant (R410A, R134a, etc.). Piping cover * The conventional leak detector for HCFC refrigerant (R22, etc.) cannot be used because its sensitivity for HFC Flare nut refrigerant lowers to approx.
  • Page 15: Applicable Control Of Outdoor Unit

    Recovery method of refrigerant • When recovering refrigerant in case of reinstallation of the indoor or outdoor unit, etc., use the refrigerant recovery switch on the terminal block of the outdoor unit. Refrigerant Work procedure recovery switch 1. Turn on the power supply. 2.
  • Page 16 This product is compliant with Directive 2002/95/EC, and cannot be disposed as unsorted municipal waste. Ce produit est conforme à la Directive 2002/95/CE et il ne peut pas être jeté avec les ordures ménagères non triées. Dieses Produkt entspricht der Richtlinie 2002/95/EWG und darf nicht als normaler, unsortierter Hausabfall entsorgt werden.

This manual is also suitable for:

Rav-sm802at-e

Table of Contents