1-10-3. Operating the High-spec Wired Remote
Controller (CZ-RTC3 / CZ-RTC5)
[
]
How to set the external static pressure
1.
Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the LCD display.
1
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
2.
Press the
If you wish to see the next screen instantly, press the
or
Select "8. Detailed settings" on the LCD display and press
the
button.
Maintenance func
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Sel.
The "Detailed settings" screen appears on the LCD display.
Select the "Unit no." by pressing the
button for changes.
Detailed settings
Unit no.
3-1
Sel.
3.
Select the "Code no." by pressing the
button.
Change the "Code no." to "B0" by pressing the
button (or keeping it pressed).
20:30 (THU)
START
,
and
20:30 (THU)
Page [
] Confirm
or
button to see each menu.
button.
20:30 (THU)
Page [
] Confirm
or
20:30 (THU)
Code no.
Set data
B0
0001
Next
or
4.
Select the "Set data" by pressing the
button.
Select one of the "Set data" among "0001" – "0015"
according to the desired external static pressure setting by
pressing the
Then press the
(See the table below.)
When setting to auto airflow volume control:
Select the setting data to "-002".
buttons
Then press the
26
External static pressure of the rated air flow
volume
0.60 in.WC (150 Pa)
0.56 in.WC (140 Pa)
0.52 in.WC (130 Pa)
0.48 in.WC (120 Pa)
0.40 in.WC (100 Pa)
0.28 in.WC (70 Pa)
0.24 in.WC (60 Pa)
0.20 in.WC (50 Pa)
0.12 in.WC (30 Pa)
0.04 in.WC (10 Pa)
No auto airflow volume setting
Auto airflow volume setting
5. Select the "Unit no." by pressing the
button and press the
The "Exit detailed settings and restart?" (Detailed setting-
end) screen appears on the LCD display.
Select "YES" and press the
When the setting is completed, perform the test run for the
external static pressure setting described in "Auto External
Static Pressure Setting Operation".
or
1-86
1. Specifications
Detailed settings
20:30 (THU)
Unit no.
Code no.
Set data
3-1
B0
0001
Sel.
Next
or
button.
button.
button.
Indoor unit
36
0.60 in.WC (150 Pa)
0.56 in.WC (140 Pa)
0.52 in.WC (130 Pa)
0.48 in.WC (120 Pa)
0.44 in.WC (110 Pa)
0.40 in.WC (100 Pa)
0.28 in.WC (70 Pa)
0.20 in.WC (50 Pa)
0.12 in.WC (30 Pa)
0.04 in.WC (10 Pa)
button.
button.
Detailed settings
20:30 (THU)
Exit detailed settings
Unit no.
Code no.
Set data
and restart?
1-1
10
0001
YES
NO
Sel.
Next
or
Item code
B0
0015
0014
0013
0012
0011
0008
0006
0005
0003
0001
-001
-002
or