Panasonic U-26PE1U6 Technical Data & Service Manual page 164

Table of Contents

Advertisement

CAUTION
If the screws are not sufficiently tightened, trouble such
as that shown in the figure below may occur.
Be sure to tighten the screws securely.
Air leakage
Air leakage
from ceiling panel
Staining
If a gap remains between the ceiling surface and the
ceiling panel even after the screws are tightened, adjust
the height of the unit again.
Adjust so that there
are no gaps.
1
(4) Wiring the Ceiling Panel
1) Open the cover of the electrical component box for control
PCB.
2) Connect the 22P connector (white) from the ceiling panel
to the connector on the control PCB in the unit electrical
component box. In this case, expose the cutout section
of the tube for the wiring protection to the outside from
the electrical component box and fix it with the clamper
attached to the electrical component box.
If the connectors are not connected, the Auto Flap will
not operate. Be sure to connect them securely. (If not
connected completely, "09" will be displayed on the
remote controller.)
Check that the wiring connector is not caught between
the electrical component box and the cover.
Check that the wiring connector is not caught between
the unit and the ceiling panel.
Electrical component
box cover
Screws (2 locations)
Cutout section of the tube
for the wiring protection
Clamper
Ceiling panel side
Main unit side
Condensation, water leakage
If there is no affect to the horizontal
of the unit and drain tube, adjustment
to the installation height of the unit
can be made through the hole of the
ceiling panel corner.
Wiring chart
(Direction that the unit
faces has been changed to
facilitate explanation.)
Ceiling panel
wiring connector
(5) How to Attach the Corner & Air-Intake Grille
A. Attaching the corner cover
1) Check that the safety cord from the corner cover is fastened
to the ceiling panel pin, as shown in the figure below.
2) Use the supplied screws to attach the corner cover to the
ceiling panel.
B. Attaching the air-intake grille
To install the air-intake grille, follow the steps for "Removing
the grille" in the reverse order. By rotating the air-intake
grille, it is possible to attach the grille onto the ceiling panel
from any of 4 directions. Coordinate the directions of the air-
intake grilles when installing multiple units, and change the
directions according to customer's requests.
When attaching the air-intake grille, be careful that the flap
lead wire does not become caught.
Be sure to attach the safety cord that prevents the air-intake
grille from dropping off to the ceiling panel unit as shown in
the figure below.
With this ceiling panel, the directions of the air-intake grille
lattices when installing multiple units, and the position of the
label showing the company name on the corner panel, can
be changed according to customer's requests, as shown in
the figure below. However, the wireless signal receiver can
only be installed at the refrigerant-tubing corner of the ceiling
unit.
Hole for ceiling panel hook
Hook that prevents the grille from dropping
Drain pipe side
Locations of air-intake
grille hinges at the
factory shipment
* The grille can be
installed with these
hinges facing in any of
4 directions.
Electrical
component box
Fig. 1-138
1-156
1. Specifications
String
Pin
Place the corner cover so that the 3 tabs
fit into the holes in the ceiling panel.
Then fasten it in place with the supplied
screws.
Refrigerant tube side
Wireless signal receiver
* Only this area
is possible for
installation.
Can be installed
rotated 90°
Fig. 1-139