6-43. Others
(1) Checking After Installation
1) Check that there are no gaps between the unit and the
ceiling panel, or between the ceiling panel and the ceiling
surface.
* Gaps may cause water leakage and condensation.
2) Check that the wiring is securely connected.
* If it is not securely connected, the auto flap will not
operate.
("P09" is displayed on the remote controller.)
In addition, the water leakage and condensation may
occur.
(2) Operating the Wireless Remote Controller
For details of installation, refer to the section "Wireless
Signal Receiver" in the supplied installation instructions.
(3) Selecting DC Fan Motor Tap (4-Way cassette 36" × 36")
Check the optional parts accordingly in the following table.
Table for DC Fan Motor Tap Setting
Remote
Setting
controller
No.
setting data
Item code 5d
0003
(3)
0003
(6)
0006
<Criteria based on the ceiling height>
Remote
Setting
controller
No.
setting data
Item code 5d
(1)
0001
Over 10.8ft. (3.3m) Over 12.8ft. (3.9m)
(3)
0003
Max. 12.8ft. (3.6m) Max. 14.8ft. (4.5m)
*1 When using optional parts in different setting No. in
combination with multiple units, conform it to the larger
setting No.
1) When setting from the P.C. Board
<Procedure>
Stop the system before performing these steps.
1 Open the electrical component box cover, then check
the indoor unit control PCB.
2 Connect the jumper connector (2P: yellow) which
was supplied with the optional parts to the correct
connector pin on the indoor unit control PCB according
to the setting number which was confirmed in Table for
DC Fan Motor Tap Setting.
Setting No. (3) :
Then connect the jumper connector to the connector
pin TP3 (2P: yellow) on the indoor unit control PCB.
Setting No. (6) :
Then connect the jumper connector to the connector
pin TP6 (2P: white) on the indoor unit control PCB.
Contents & optional parts name
Air-blocking material
(for 3-way air discharge)
Air-blocking material
(when a discharge duct is
connected)
Air-blocking material
(for 2-way air discharge)
S-36PU2U6
S-26PU2U6
S-42PU2U6
2) When setting with the Wired Remote Controller
<Procedure of CZ-RTC2>
Stop the system before performing these steps.
1 Press and hold the
simultaneously for 4 seconds or longer.
2 If group control is in effect, press the
and select the address (unit No.) of the indoor unit
to set. At this time, the fan at the indoor unit begins
operating.
3 Designate the item code
Temperature Setting
4 Press the timer time
desired setting data.
* For item codes and setting data, refer to "Table for DC
Fan Motor Tap Setting".
5 Press the
button.
(The display stops blinking and remains lit, and setting
is completed.)
* If air-blocking material is used, use the same
procedure as in steps 3 – 5 above and change the
setting for item code "62" to "0000".
If you wish to change the selected indoor unit, follow
the step 2.
6 Press the
button to return to normal remote
controller display.
6
1
5
1-157