Cold Draft Prevention (Heating Cycle) - Panasonic U-26PE1U6 Technical Data & Service Manual

Table of Contents

Advertisement

2-2. Cold Draft Prevention (Heating Cycle)

The cold draft prevention function controls indoor fan speed so a strong draft of cold air will
not blow out before the indoor heat exchange coils have warmed up.
STANDBY shows on the remote controller when the indoor fan speed is LL (very low)
or OFF. This condition occurs in the following 3 cases:
• During Thermo OFF (refer to 2-1 B. Room Temperature Control, Heating)
• During the defrosting operation (refer to the section "Defrost Control" on page 2-8)
• Until either the coil temperature E2 reaches 72°F(Type F2, T2) or 68°F(Type U2)
or 81°F(Type U1,K1,T1,F1, K2) or when a maximum of 6 minutes have passed.
The indoor fan motor operates in L instead of LL for 3 seconds as it starts to give the
fan an initial boost.
Type F2,T2
INDOOR UNIT
COIL TEMP.
E2 (°F)
2
SET
FAN
SPEED
"STANDBY"
INDICATOR
The main idea of this chart is to show that the indoor fan speed increases and gets closer to
the set fan speed as the coil temperature E2 rises.
The indoor unit's coil temperature is taken from sensor E2 located in the middle of the indoor
heat exchange coil.
The dotted line shows that the indoor fan motor is OFF. When the temperature at sensor E2
falls below 50 ˚F, the indoor fan motor stops running.
U2
U1,K1,T1,F1,K2
79
75
92
MAX. 6 MINUTES
75
72
88
72
68
81
68
64
77
50
46
50
AUTO OR H
LL
LL/OFF
M
LL
LL/OFF
L
LL
LL/OFF
"STANDBY" APPEARS
LL= Very low speed
L= Low speed
Chart Summary and Explanations
LL
L
M
LL
L
M
LL
L
L
M= Medium speed
H= High speed
2-4
2. Processes and functions
H
M
L
1135_THS_I
Fig. 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents