II Restrictions

[1] System configuration

1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.

(1) Standard combinations

Outdoor
Composing units
units
200
-
250
-
300
-
350
-
400
-
450
200
500
250
550
250
600
300
650
300
700
300
750
350
800
400
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.

(2) High COP combinations

Outdoor
Composing units
units
200
-
300
-
400
200
450
200
500
200
550
250
600
300
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE07130
Maximum total capacity
of connectable indoor
units
-
100 - 300
-
125 - 375
-
150 - 450
-
175 - 525
-
200 - 600
250
225 - 675
250
250 - 750
300
275 - 825
300
300 - 900
350
325 - 975
400
350 - 1050
400
375 - 1125
400
400 - 1200
Maximum total capacity
of connectable indoor
units
-
100 - 300
-
150 - 450
200
200 - 600
250
225 - 675
300
250 - 750
300
275 - 825
300
300 - 900
Maximum number
of connectable in-
door units
20
P15 - P250 models
R410A series indoor units
25
30
35
40
45
50
Maximum number
of connectable in-
door units
20
P15 - P250 models
R410A series indoor units
30
40
45
50
- 17 -
Types of connectable in-
door units
Types of connectable in-
door units
GB