Abnormal Bus Voltage Drop (Detail Code 108) - Mitsubishi Electric PURY-(E)P200 Service Handbook

Hide thumbs Also See for PURY-(E)P200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
1. Error Code
4220
4225

Abnormal bus voltage drop (Detail code 108)

2. Error definition and error detection method
If Vdc 289V or less is detected during Inverter operation. (S/W detection)
3. Cause, check method and remedy
(1) Power supply environment
Check whether the unit makes an instantaneous stop when the detection result is abnormal or a power failure occurs.
Check whether the power voltage (Between L1 and L2, L2 and L3, and L1 and L3) is 342V or less across all phases.
(2) Voltage drop detected
4220
Check the voltage between the FT-P and FT-N terminals on the inverter board while the inverter is stopped and if it is 420 V
or above, check the following items.
1) Confirm on the LED monitor that the bus voltage is above 289V.
Replace the inverter board if it is below 289 V.
2) Check the voltage at CN72 on the control board. ->Go to (3).
3) Check the noise filter coil connections and for coil burnout.
4) Check the wiring connections between the following sections
Between the noise filter board and inverter board. Between the inverter board and DCL.
Replace 72C if no problems are found.
5) Check the IGBT module resistance on the inverter board (Refer to the Trouble shooting for IGBT module).
Check the voltage between the FT-P and FT-N terminals on the inverter board while the inverter is stopped and if it is less
than 420 V, check the following items.
1) Check the coil connections and for coil burnout on the noise filter.
2) Check the wiring between the noise filter board and inverter board.
3) Check the connection to SCP1 and SC-P2 on the inverter board.
4) Check the in-rush current resistor value.
5) Check the 72C resistance value.
6) Check the DCL resistance value.
Replace the inverter board if no problems are found.
4225
Check the voltage at CNVDC on the fan inverter board while the inverter is stopped and if it is 420 V or above, check the
following items.
1) Check the voltage at CN72 on the control board. ->Go to 3).
2) Check the noise filter coil connections and for coil burnout.
3) Check the wiring connections between the following sections
Between the inverter board and the fan board.
4) Check contents 4220
Replace the fan board if no problems are found.
Check the voltage at CNVDC on the fan inverter board while the inverter is stopped and if it is less than 420 V, check the
following items.
1) Check the state of the wiring connections between the inverter board and the fan board.
2) Check contents 4220
Replace the fan board if no problems are found.
(3) Control board failure
Confirm that DC12V is applied to the connector CN72 on the control board while the inverter is operating. If not, replace the
control board.
Refer to section - 7 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 271)
HWE07130
- 194 -
GB