[ IX Troubleshooting ]
1. Error Code
6607
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System configuration
(2) Grouping of units in a system with multiple outdoor units
Error
source
Error display
address
LOSS-
M-NET re-
NAY
mote controller
(LC)
(RC)
MA remote
controller (MA)
HWE07130
Detection
method
No acknowl-
(1)
Factors (1) through (5) in the
edgement
"Factors in system with one
(ACK) at IC
outdoor unit" (When perform-
transmission to
ing an interlocked operation
LC
of the LOSSNAY unit and the
indoor units that are connect-
ed to different outdoor units.)
(2)
Disconnection or short circuit
of the transmission line for
the outdoor unit on the termi-
nal block for centralized con-
trol line connection (TB7)
(3)
When multiple outdoor units
are connected and the power
source of one of the outdoor
units has been shut off.
(4)
The male power supply con-
nector of the outdoor unit is
not connected to the female
power supply switch connec-
tor (CN40).
(5)
The male power supply con-
nectors on 2 or more outdoor
units are connected to the fe-
male power supply switch
connector (CN40) for central-
ized control.
If an error occurs, after the
unit runs normally once, the
following causes may be con-
sidered.
- 216 -
Cause
1)
2)
3)
Total capacity error
(7100)
Capacity code error
(7101)
Error in the number of
connected units (7102)
Address setting error
(7105)
Check method and remedy
Turn off the power source of
LOSSNAY for 5 or more min-
utes, and turn it on again. If the
error is accidental, it will run
normally.If not, check the
cause 2).
Check the causes of (1) - (5). If
the cause is found, correct it. If
no cause is found, check 3).
Same cause as that for indoor
unit described in 3)