Cooling Only Operation; Standard Operation Data (Reference Data) - Mitsubishi Electric PURY-(E)P200 Service Handbook

Hide thumbs Also See for PURY-(E)P200:
Table of Contents

Advertisement

[ VIII Test Run Mode ]

[7] Standard Operation Data (Reference Data)

1. Single unit

(1) Cooling only operation

Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE07130
Operation
Indoor
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger outlet
PURY-P200YHM-A
CMB-P104V-G
27°C/19°C
[81°F/66°F]
DB/WB
35°C/-
[95°F/-]
2
Unit
2
-
112/112
5 [16-3/8"]
m
10 [32-3/4"]
[ft]
25 [82]
-
Hi
kg
14.8 [33]
[lbs-oz]
A
20.5
V
200
Hz
52
325/325
Pulse
2000/-/160
2.96/0.80
[429/116]
MPa
[psi]
2.81/2.81
[408/408]
90 [194]
39 [102]
8 [46]
°C
8 [46]
[°F]
19 [66]
47 [117]
19 [66]
6 [43]
- 153 -
Outdoor unit model
PURY-P250YHM-A
CMB-P104V-G
27°C/19°C
[81°F/66°F]
35°C/-
[95°F/-]
2
2
140/140
5 [16-3/8"]
10 [32-3/4"]
25 [82]
Hi
18.5 [41]
26.8
200
65
387/387
2000/-/170
2.96/0.78
[429/113]
2.81/2.81
[408/408]
85 [185]
39 [102]
8 [46]
8 [46]
19 [66]
40 [104]
19 [66]
6 [43]
GB