Mitsubishi Electric PURY-(E)P200 Service Handbook page 278

Hide thumbs Also See for PURY-(E)P200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
Check whether the BC board output signal corresponds with the solenoid valve operation correspond.
1) SVA, SVB, SVC
SVA, SVB, and SVC turn on or off according to the indoor unit operation mode.
Port
SVM1, SVM1b, SVM2, SVM2b
SVM1, SVM1b, SVM2, and SVM2b turn on or off according to the indoor unit operation mode.
Operation
mode
SVM1,SVM1b
SVM2,
SVM2b
2) SVA, SVB, SVC
Measure the temperature at the upstream and downstream pipes
Measure the temperature at the upstream and downstream
HWE07130
Cooling
SVA
ON
SVB
OFF
SVC
ON
Cooling only
Cooling main
Pressure dif-
ferential con-
ON
trol OFF or
ON
OFF
OFF
Mode
Heating
Stopped
OFF
OFF
ON
OFF
OFF
OFF
Heating only
Heating main
OFF
OFF
Pressure dif-
Pressure dif-
ferential con-
ferential con-
trol OFF or
trol OFF or
ON
ON
and
of SVA.
pipes and
of SVA.
- 269 -
Defrost
Fan
OFF
OFF
OFF
OFF
OFF
ON
Defrost
Stopped
ON
OFF
OFF
OFF
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents