Horizontal Term. With Three Vert. Elbows - FireplaceXtrordinair 44 DV XXL Owner's Manual

Hide thumbs Also See for 44 DV XXL:
Table of Contents

Advertisement

Installation
2 2
Horizontal Terminations with Three Vertical Elbows
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.
NOTE:
¥ A total of three elbows must be used.
¥ No horizontal elbows may be used (a horizontal elbow is defined
as an elbow that directs the vent from a horizontal direction to
another horizontal direction).
¥ Two 45¡ elbows may be substituted for two of the 90¡ elbows.
¥ Horizontal sections require a 1/4" rise every 12" of travel.
¥ The maximum vertical height is 19'.
¥ The maximum horizontal length is 20'.
19' (max)
15 feet
10 feet
5 feet
0 feet
Travis Industries
(for qualified installers only)
Horizontal Elbows are
NOT ALLOWED
NOTE:
Restrictor positions are based upon
lab tests. The ideal restrictor position
may vary slightly.
Min. 24" Rise
Before First Elbow
9 3 5 0 8 1 0 9
Restrictor
Position #2
Restrictor
Position #1
19' (max)
15 feet
10 feet
5 feet
0 feet
1 8 0 5 0 1