Vent Requirements; Altitude Considerations; Clearances; Part Numbers (8" Dia. Pipe) - FireplaceXtrordinair 44 DV XXL Owner's Manual

Hide thumbs Also See for 44 DV XXL:
Table of Contents

Advertisement

Installation

Vent Requirements

!
The vent must maintain the required clearance to combustible materials to prevent a fire (see
ÒClearancesÓ below). Do not fill air spaces with insulation.
!
The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use it's own separate vent system.

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 8,000 feet (2,400 M). In this testing we have
found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
!
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.

Clearances

Horizontal Runs
The Travis firestop is required
(part # 93006094) when passing
Min. 5-1/2" Clearance
through any wall.
Above the Vent
(before first firestop)
Min. 18" rise before
first elbow.
Min. 75"
(from base
of fireplace)
Part Numbers for 8" Diameter Vent
Use 8Ó diameter Model GS Direct Vent manufactured by Simpson Dura-Vent only . Follow the
installation instructions included with the vent. For the nearest Simpson Dura-Vent supplier, call (800)
835-4429. Vent part numbers and descriptions are listed below.
Straight Lengths
1208B
6" Pipe Length, Black
1207B
9" Pipe Length, Black
1206B
12" Pipe Length, Black
1204B
24" Pipe Length, Black
1203B
36" Pipe Length, Black
1202B
48" Pipe Length, Black
1211B
11Ó to 14-5/8" Adjustable, Black
Travis Industries
(for qualified installers only)
Min. 3" Clearance Above 45¡
Sloping Vent after first firestop
(5-1/2" before first firestop)
Min. 3" Clearance
Above the Vent
(after first firestop)
Min. 1" Clearance to the
Sides & Below the Vent
(before or after the firestop)
Terminations
1284
Horizontal Square Termination
1285
Hor. High Wind Termination
1250
Vinyl Siding Stand-off
1291
Travis Vertical Termination
Elbows
1245B
45¡ Elbow, Black
1290B
90¡ Elbow, Black
9 3 5 0 8 1 0 9
Vertical Sections
Min. 1" Clearance to the
Sides & Below the Vent
(before or after the firestop)
Min. 75"
(from base of fireplace)
Penetration, Support
93006094 Travis Firestop
1241
1288
1263
1 7
Use the Simpson ceiling
firestop (#1263)
whenever passing
through a ceiling (or
enclosure and at every
floor penetration.
Cathedral Ceiling Support Box
Wall Strap
Ceiling Firestop
1 8 0 5 0 1