Page 1
PACKAGE STANDBY SYSTEMS PSS50LS-*/A INSTALLATION AND OPERATIONS MANUAL PSS65LS-*/A PSS50LS-*/B PSS65LS-*/B Engine Generator Set Automatic Transfer Switch 225 SOUTH CORDOVA AVE LE CENTER MN 56057 507-357-6831...
“Things To Check” near the end of this manual. The war- Coolant ranty listed in this manual describes what you can expect Battery Installation from WINCO should you need service assistance in the fu- BATTERY TNDER & BLOCK HEATER WIRING ture TRANSFER SWITCH INSTALLATION...
SAFETY INFORMATION 2. FIRE HAZARD - Natural gas and L.P. present a hazard of possible explosion and/or fire. This engine generator set has been designed and a. Do not smoke or use open flame near the generator manufactured to allow safe, reliable performance. Poor set.
TESTING POLICY: mechanically interlocked. A seven day electronic exer- ciser clock are installed in the A.T.S. as standard equip- Before any generator is shipped from the factory, it is ment. The A.T.S. also contains the power failure sensing fully checked for performance. The generator is loaded to circuitry necessary to send a start/stop signal to the engine its full capacity, and the voltage, current, and frequency generator set.
water temperature shutdown has a 60 to 90 second lock- The engine manufacturer has established an excellent out, allowing the engine time to clear the hot water out of world-wide engine service organization; engine service is the block in case of a hot restart. In addition if the genera- available from a nearby authorized dealer or distributor;...
INSTALLATION FUEL INSTALLATION General Information The fuel supply should be as close as possible to the engine. This will reduce the installation cost of fuel runs. The information in this manual is offered to assist you in ************* providing the proper fuel for your engine. However, this ***** WARNING **** information is only provided to inform you of the engine’s *************...
generally adequate for distances up to 300 feet from the primary to the secondary regulator. (Consult your local Fuel Pressure Table fuel supplier for your exact requirements). The appropriate line size from the table below is then installed from the Single Regulator (L.P.
NOTE: Alway make sure that a new battery is fully Tank Fuel Solenoid Converter Engine charged before installing it on a generator set. Failure to do so can cause damage to the engine control module in the generator set. Reference number 1 is the fuel tank. No regulator is re- quired but the tank must have a liquid withdrawal drop tube All connections must be clean and tight.
*****NOTE***** EQUIPMENT DAMAGE- The standard single phase Winco ATS does not protect against undervoltage. If you are in an area that is susceptible to brown outs (low volt- age) you may want to consider adding an undervoltage sensor to standard ATS panel.
Page 10
The line terminals in the A.T.S. are marked “LINE - L1, L- ************* N, L3”. The “hot” leads L1 and L3 will wire directly to the ***** WARNING ***** top lugs on the line side contactor. The L-N connection will ************* be made at the neutral bar on the standoffs on the floor of EQUUIPMENT DAMAGE - When installing a Three...
EQUIPMENT DAMAGE - DC connections between age should be 240 A.C. and a frequency of 60 (Hz). If you Winco engine generators and other makes of Automatic have the proper voltage at the generator the next step is to Transfer Switches will vary. The Winco engine generator...
** Notice ** 3. Push the "Hour Select Button" until the display indi cates the correct time in hours. Note: In the afternoon If for any reason during the check out procedure the volt- you should push the button until a "P" is displayed be age and frequency are not correct, turn the selector switch side the correct hour.
If, when you finish programing the clock, you get an ENGINE STARTS AND THEN STOPS AND FAULT EEEE on the display, it stands for error. The most com- LIGHT COMES ON mon error is that the day of operation has not been prop- erly set at each step or a progam has been turned on and 1.
LP/NG FUEL ADJUSTMENTS FUEL TYPE CONVERSION If it should be necessary to change the type of fuel being **** CAUTION **** used after the unit has been shipped from the factory it will EQUIPMENT DAMAGE - Do not make any fuel adjust- be necessary to change the air gas valve assembly in the ments or governor adjustments until all pressure readings vapor fuel carburetor.
Page 15
PROPANE VAPOR TO NATURAL GAS 1. Turn off fuel supply. 2. Remove the fuel line from the carburetor at the demand regulator. 3. Invert the regulator so the column is in the upright position. Remove the cap on the upright column of the regulator.
VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE CONTROL PANEL WIRING THREE PHASE AND SINGLE PHASE THREE SINGLE PHASE PHASE 1017-10 Page 16 60706-144...
To the extent permitted by law, any and all warranties, including those of merchantability and fitness for a particular purpose, are limited to 12 months from date of purchase. In no event is WINCO liable for incidental or consequential damages.