ENGINE CONTROL PANEL LAYOUT To Check” near the end of this manual. The warranty listed DSE 7110 CONTROLLER in this manual describes what you can expect from WINCO INITIAL START-UP should you need service assistance in the future. START-UP PROCEDURE...
FIRE HAZARD - NG and LP present a hazard of possible IMPORTANT SAFETY explosion and/or fire. INSTRUCTIONS Do not smoke or use open flame near the generator set. Keep a fire extinguisher nearby and know its proper use. SAVE THESE INSTRUCTION Fire extinguishers rated ABC by NFPA are appropriate.
120/240 ¨ Five-key Menu Navigation PSS90-18 277/480 ¨ Engine Exercise Mode Additional optional A.T.S. sizes are available to meet specific needs. Contact your local WINCO dealer or the WINCO Sales Department for a quote. 1270-10 REV B Page 2 60706-213...
FUNCTIONS ENGINE SPECIFICATIONS: DSE 7110 Series Control Modules perform the following protec- tion and metering functions: Refer to engine operating and maintenance instructions Generator Protection and Metering ** NOTICE ** Generator protection includes over voltage, under voltage, under Regarding Engines - This manual covers the generator portion of frequency, over frequency and overload protection.
These units should be mounted to allow for ample working room UNPACKING: around it. Units must be installed in accordance with all local, state and national codes. Consult your local agency having Carefully remove the carton. After inspecting the engine-generator for external physical jurisdiction for specific requirements.
Two (2) Regulator System (L.P. Vapor only) *************** **** WARNING **** *************** UNIT OFF TANK PSI 10-15 lbs 7-11 in 7-11 in PERSONAL DANGER - Do not use galvanized pipe in fuel line 4-6 oz 4-6oz runs. The galvanized coating can become eroded and flake off, STARTING TANK PSI 10-15 lbs...
INSTALLING THE BATTERY ately with water and seek immediate medical attention. Spilled electrolyte is to be washed down with an acid neutral **** CAUTION **** izing agent. A common practice is to use a solution of one pound of bicarbonate of soda (baking soda) to one gallon of In the following battery installation procedure, check to be sure water.
duplex receptacle is mounted on the generator along side circuit breaker panel, the battery tender is shipped already plugged into the receptacle. The engine blockheater installed on this unit\ should also be plugged in this receptacle. The block heater is thermostatically controlled and when plugged in will maintain the engine coolant temperature between 100 and 120 degrees F.
C - Ground Lug, These ground lugs are bonded to ground and are provided for you to connect your ground wire from the transfer switch to. The lugs on the 80 kW will handle wire sizes #1 AWG to 300 MCM and should be torqued to 250 in. lbs. The lugs on the 60 kW will accommodate #1 AWG to 250 MCM and should be torqued to 250 in.
DC Interconnections to the Automatic Transfer Switch ASCO 300 UL SWITCH Your DC connection points in the ASCO 300 ATS are terminals Two control wires are required between the A.T.S. panel and the “14” and “15”. Depending on the size of the switch they are generator control terminal box.
D. AC INTERFACE CONNECTOR - This connector is used to received while this switch is activated, the unit will not start. interface with the AC generator end. It provides the controller with the voltage, amperage and frequency reading for the display. C.
motor is disengaged and goes into a rest mode after which a INITIAL START UP second attempt is made to start the engine. Should this se- quence continue through 3 cranking cycles the start sequence **************** will be stopped and the display will show ‘FAILED TO START’. ***** WARNING ***** 3.
To test the automatic start Transfer Switches follow the instruction ENGINE STARTS AND THEN STOPS AND ALARM in the operator’s manual you received with your transfer switch. If LIGHT COMES ON you get a fault light during the initial start up or prior to start up it is most likely a false warning light.
CHANGING THE FUEL TYPE **** CAUTION **** EQUIPMENT DAMAGE - Do not make any fuel adjustments or governor adjustments until all pressure readings are in compli- ance with specification. See fuel pressure charts (tables 1, 2, and 3). These engine/generator sets are very easy to convert between LP or NG.
WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product. At WINCO’s option, material found to be defective in material or workmanship under normal use and service will be repaired or replaced. For warranty service,...