Outdoor Temperature Sensor - Viessmann Vitodens 200 WB2 Installation Instructions Manual

Wall-mounted, gas-fired condensing boiler
Table of Contents

Advertisement

Control unit
Connections to control unit

Outdoor temperature sensor

1.
2.
12
5862130G - page 12 (Black)
Screen angle and frequency: 45.0000, <default>
3.
X6
5.
1 2
3
4
1. Remove the cap.
2. Mount the bottom part of the case
(cable entry must point down
wards).
4.
Please note:
The outdoor temperature sensor
should be mounted 2 to 2.5
metres above ground level on the
north or north-west facing wall of
the building. In the case of multi-
storey buildings, it should be
mounted in the upper half of the
second storey.
Make sure that the sensor is not
located over windows, doors and
air vents, nor immediately be
neath a balcony or guttering.
The outdoor temperature sensor
must not be plastered over. If
mounting on an unplastered wall,
make allowances for thickness of
plaster or remove sensor before
plastering wall.
3. Connect the cable to the terminals
(the wires are interchangeable).
Cable:
2
2 × 1.5 mm
, max. 35 m long,
copper.
Please note:
Do not run cable immediately next
to 230/400 V cables.
4. Place cap over base and snap on.
5. Connect the outdoor temperature
sensor to the connector "X 6" (the
wires are interchangeable).