Installation Requirements - Lenovo 5594-6KX Installation And User Manual

Hide thumbs Also See for 5594-6KX:
Table of Contents

Advertisement

Procedure
1. Remove the connector panel blank (
2. Insert the UPS Network Management Card into the slot. Secure the panel by

Installation requirements

Recommended protective devices and cable cross-sections
1. Recommended upstream protection
2. Recommended cable cross-sections
24
Installation and User's Guide
tightening the two screws.
UPS power rating
5000VA
6000VA
Terminal
position
Wire function
L1
Phase
N(L2)
Neutral
Ground
Copper wire, solid or stranded.
), which is secured by two screws.
Upstream circuit breaker
D curve – 30A
D curve – 30A
Terminal wire
Minimum input
size rating
wire size
2
2
4-16 mm
(12-6
6 mm
AWG)
105°C
2
10 mm
75°C
Tightening
torque
(10 AWG)
10 lb in / 1.13
Nm
(8 AWG)

Hide quick links: