Lenovo 5594-6KX Installation And User Manual page 31

Hide thumbs Also See for 5594-6KX:
Table of Contents

Advertisement

Submenu
On/Off settings
Cold start
Forced reboot
Auto restart
Auto start
Energy saving
Available settings
Default settings
[Enabled] [Disabled]
[Enabled]
Authorize the
product to start on
battery power.
[Enabled] [Disabled]
[Enabled]
If mains recover
during a shutdown
sequence:
If set to Enabled,
shutdown sequence
will complete and
wait 10 seconds prior
to restart, if set to
Disabled, shutdown
sequence will not
complete and restart
will occur
immediately.
[Enabled] [Disabled]
[Enabled]
Authorize the
product to restart
automatically when
mains recovers after
a complete battery
discharge.
[Enabled] [Disabled]
[Disabled]
The UPS
automatically starts
up as soon as mains
power is available
(no need to press the
button).
[Disabled] [100W] ...
[Disabled]
[1000W]
If Enabled, UPS will
shut down after 5
min. of back-up time,
if load is less than
threshold.
Chapter 2. Presentation
13