10

Mobile Home

A. Mobile Home Installation
You must use an authorized Outside Air Kit
for installation in a mobile home.
1.
An outside air inlet must be provided for the combustion
air and must remain clear of leaves, debris, ice and/or
snow. It must be unrestricted while the appliance is in
use to prevent room air starvation which causes smoke
spillage. Smoke spillage can also set off smoke alarms.
2.
The combustion air duct system must be made of metal.
It must permit zero clearance to combustible construc-
tion and prevent material from dropping into the inlet or
into the area beneath the dwelling and contain a rodent
screen.
3.
The appliance must be secured to the mobile home
structure by bolting it to the fl oor (using lag bolts) with
two attachment points. Use the holes in the appliance
base.
4.
Ground wire to be connected directly to the frame of the
manufactured home.
5.
Refer to Clearances to Combustibles and fl oor protection
requirements for listings to combustibles and appropriate
chimney systems.
6.
Use silicone to create an effective vapor barrier at the
location where the chimney or other component pen-
etrates to the exterior of the structure.
7.
Follow the chimney manufacturer's instructions when
installing the vent system for use in a mobile home.
8.
Installation shall be in accordance with the Manufactur-
ers Home & Safety Standard (HUD) CFR 3280, Part 24.
WARNING
Installation must comply with Manufactured Home and
Safety Standard (HUD), CFR 3280, Part 24.
WARNING
Asphyxiation Risk
NEVER INSTALL IN A SLEEPING ROOM.
Consumes oxygen in the room.
30
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME
FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED
Do NOT cut through:
• Floor joist, wall, studs or ceiling trusses.
• Any supporting material that would affect the structural
integrity.
Never draw outside combustion air from:
Wall, fl oor or ceiling cavity
Enclosed space such as an attic, garage or crawl space.
Storm Collar
Joist Shield/Firestop
7086-171I • May 6, 2015
CAUTION
CAUTION
Spark Arrestor Cap
Roof Flashing
Approved Class "L"
or "PL" Pellet Vent
www.pelprostoves.com