Step 6 Wait until the pre-chill cycle begins, then
jumper water level probe connection #2 & #3 at the
control board.
A. Water level light energizes and water flow
stops - Repair wire or replace water level
probe.
B. Water level light does not energize and water
continues to flow - Replace control board.
WATER TROUGH OVERFILLING CONTINUED
Step 6. Water level probe wires #2 & #3 jumpered
at the control board connector
Is Water
Flowing
into the
Water
Trough?
No
Yes
Yes
Part Number STH026 2/12
The
The Water
Water
Inlet Valve
Level
Solenoid
Light
Is:
On
De-energized
Off
Energized
On
De-energized
Coil Is:
Cause
The
interconnecting
wire or water level
probe is causing
the problem.
Ohm, then clean or
replace the water
level probe or wire.
The control board
is causing the
problem.
The water fill valve
is causing the
problem.