(d) In addition to air needed for combustion, air shallbe
supplied forventilation, including allairrequired forcomfort
andproper w orking c onditions forpersonnel.
(e)While allforms ofbuilding c onstruction
cannot becovered
indetail,
a ir for combustion,
ventilation
and dilution
of flue
gases
for gas utilization
equipment
vented
by natural
draft
normally
may
be obtained
by application
of one
of the
methods
covered
in 5.3.3
and 5.3.4.
(f) Air requirements
for the operation
of exhaust
fans,
kitchen
ventilation
systems,
clothes
dryers,
and fireplaces
shall
be
considered
in determining
the adequacy
of a space
to
provide
combustion
air requirements.
5.3.2 Equipment
Located
in Unconfined
Spaces:
In unconfined
spaces
(see
definition
below)
in buildings,
infiltration
may be adequate
to provide
air for combustion
ventilation
and dilution
of flue gases.
However,
in buildings
of tight construction
(for example,
weather
stripping,
heavily
insulated,
caulked,
vapor
barrier,
etc.),
additional
air may
need
to be provided
using the methods
described
in 5.3.3-
b or 5.3.4.
Space,
Unconfined.
For purposes
of this Code,
a space
whose
volume
is not
less
than
50 cubic
feet
per
1,000
BTU
per hour
of the
aggregate
input
rating
of all appliances
installed
in that
space.
Rooms
communicating
directly
with
the space
in
which
the appliances
are
installed
through
openings
not
furnished
with
doors,
are
considered
a part
of the
unconfined
space.
5.3.3 Equipment
Located
in Confined
Spaces:
(a) All Air
from
Inside
the Building:
The
confined
space
shall
be provided
with
two permanent
openings
communicating
directly
with
an additional
room(s)
of sufficient
volume
so
that the combined
volume
of all spaces
meets
the criteria
for an unconfined
space.
The total
input of all gas utilization
equipment
installed
in the
combined
space
shall
be
considered
in making
this
determination.
Each
opening
shall
have a minimum
free area of 1 square
inch per 1,000
BTU
per hour
of the total
input
rating
of all gas utilization
equipment
in the
confined
space,
but not less
than
100
square
inches.
One
opening
shall
be within
12 inches
of
the top
and
one within
12 inches
of the
bottom
of the
enclosure.
NOTE: Each opening
must have
a free area of not less than one
square
inch per 1000 BTU of
the total input rating
of all equip-
ment in the enclosure,
but not
less than 100 square
inches.
Chimney
or Gas Ve_t
.....................
...................
rll
i .LI
--Opeo,o
Equipment
Located
in Confined
Spaces;
All Air from
Inside
Building.
See 5.3.3-a.
the
bottom
of
the
enclosure.
The
openings
shall
communicate
directly,
or by ducts,
with
the outdoors
or
spaces
(crawl
or attic)
that
freely
communicate
with
the
outdoors.
1. When
directly
communicating
with
the outdoors,
each
opening
shall
have
a minimum
free
area
of 1 square
inch per 4,000
BTU
per hour of total
input
rating
of all
equipment
in the enclosure.
NOTE: The inlet and outlet air
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total input rating of alt equipment
in the enclosure.
unheated
rlawl space
Equipment
Located
in Confined
Spaces;
All Air from
Outdoors--
Inlet Air from
Ventilated
Crawl Space
and Outlet Air to Ventilated
Attic, See 5.3.3-b
2. When communicating
with the outdoors through vertical
ducts, each opening shall have a minimum free area of
1 square
inch per 4,000 BTU per hour of total input
rating of all equipment
in the enclosure.
j
_¢himney
or Gas Ve_t
i
Venti_aUon louvers
i
-J-
(each end ot att4c)
NOTE:
The
inlet
and
outlet
air
openings
must
each
have
a free
area
of not less
than
one
square
inch
per
4000
BTU
of the
ot tro et
©_t]etAr
in
the enclosure.
water
Heater
Inlet
air
duct
/end,
I ft (300
ram)
ve _ooq
Equipment
Located
in Confined
Spaces;
All Air from
Outdoors
Through
Ventilated
Attic,
See 5.3.3-b.
3. When
communicating
with
the
outdoors
through
horizontal
ducts,
each
opening
shall
have
a minimum
free area
of 1 square
inch per 2,000
BTU
per hour of
total
input
rating
of all equipment
in the enclosure.
Ch
mney
or Gas
Vent
NOTE:
The
air
duct
openings
must
have
a free
area
of not
less
than
one
square
inch
per
2000
BTU
of the
total
input
rating
of all equipment
in the
enclosure*.
(b) AllAir
from Outdoors."
The confined
space
shall be provided
Equipment
Located
in Confined
Spaces;
All Air from
Outdoors
-
with two permanent
openings,
one commencing
within
12
See &3.3-b.
inches
of the top and one commencing
within
12 inches
of