TROUBLESHOOTING
CHART
• Circulator
blower
runs
continuously.
No furnace
operation.
• Integrated
control module
diagnostic
LED is flashing
FOUR (4) flashes.
• Induced
draft blower and
circulator
blower
runs
continuously.
No furnace
operation.
• Integrated
control module
diagnostic
LED is flashing
FIVE (5) flashes.
• Furnace fails to operate.
• Integrated control module
diagnostic
LED is flashing
SIX (6) flashes.
• No furnace
operation.
NormaI furnace
operation.
Integrated
control
module diagnostic
LED
is flashing SEVEN (7)
flashes.
Induced draft blower runs
continuously.
No furnace
operation.
Integrated control module
diagnostic LED is flashing
continuously.
4 FLASHES
5 FLASHES
÷
6 FLASHES
÷
7 FLASHES
÷
CONTINUOUS
FLASHING
• Primary limit
circuit is open.
Flame sensed
with no call
for heat.
Rollout limit open.
Integrated
control
module fuse is
blown.
• Flame sense
mlcroamp signal is
low.
• Polarity of 115
or 24 volt
)ower
is
reversed.
• Insufficient
conditioned
air
over the heat exchanger.
Blocked filters, restrictive
ductwork,
improper
circulator
blower
speed, or
failed circulator
blower.
• Faulty primary limit switch.
• Loose or improperly
connected
wiring.
Short to ground in flame
sense circuit.
• Flame rollout.
• Misaligned
burners,
blocked flue and/or air
inlet pipe, or failed
induced
draft blower.
• Loose or improperly
connected
wiring.
• Short in 24 volt AC
control
circuits or
safety
circuits.
•Faulty rollout limit.
Flame sensor is coated/
oxidized.
Flame sensor incorrectly
)ositioned
in burner
flame.
Lazy burner flame due to
improper
gas pressure
or combustion
air.
• Polarity of 115 volt AC
power to furnace
or
integrated
control module
is reversed.
• Red and blue wires to
transformer
are
reversed.
• Poor unit ground.
STEADY
Normal operation.
• LED is steady on
ON
• Check primary limit.
Replace
if necessary.
• Check filters and
ductwork
for blockage.
Clean filters or remove
obstruction.
• Check circulator
blower
speed and performance.
Correct speed or
replace
blower
if
necessary.
• Tighten
or correct wiring
connection.
• Correct short at flame
sensor or in flame
sensor
wiring
• Check burners for proper
alignment.
• Check flue and air inlet
piping for blockage,
proper length, elbows,
and termination.
Correct
as necessary.
• Check rollout limit.
Replace if necessary.
• Check induced
draft
blower
for proper
performance.
Replace,
if
necessary.
• Tighten
or correct wiring
connection.
• Repair short in 24 volt AC
control/safety
circuit(s).
• Replace integrated
control
module fuse (3A).
• Sand flame sensor.
• Inspect for proper sensor
alignment.
• Compare current gas
pressure
to rating plate
info.
Adjust as needed.
• Review wiring diagram
to
correct
polarity.
• Verify proper ground.
Correct
if necessary.
• Reverse red and blue
wires connected
to
transformer.
2 LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
3O
• Turn power OFF
prior to repair.
• Replace primary
switch
with
proper
replacement
part.
• Replace blower
with
correct
replacement
part.
Turn power
OFF prior to
re )air.
• See "Vent/Flue
Pi)e" section for
piping details.
• Replace induced
draft
blower
with proper
re )lacement
)art.
• Replace
integrated
control
module fuse with
3A automotive
fuse.
• Read precautions
in "Electrostatic
Discharge"
section of
manual.
• Replace rollout
limit with correct
re 3lacement
)art.
• Turn power OFF
prior to repair.
• Clean flame
sensor with steel
wool.
• See "Vent/Flue
Pi 3e" section for
piping details.
• See rating plate
for proper gas
)ressure.
• Turn power OFF
prior to repair.