Troubleshooting Chart - Goodman GMH8 Installation Instructions Manual

Gas-fired warm air furnace
Table of Contents

Advertisement

TROUBLESHOOTING
CHART
Furnace fails to operate.
Integrated
control
module diagnostic
LED
provides
no signal.
, Furnace fails to operate
Furnace fails to operate.
Integrated
control
module diagnostic
LED
is flashing ONE (1)
flash.
Furnace fails to operate.
Integrated
control
module diagnostic
LED
is flashing TWO (2)
flashes.
• Induced
draft blower
runs continuously
with
no further
furnace
operation.
• Integrated
control
module diagnostic
LED
is flashing THREE (3)
flashes.
NONE
• No 115 volt power
to furnace,
or no 24
volt power to
integrated
control
module.
• Manual
disconnect
switch
OFF, door switch open, or
24 volt wires improperly
connected
or loose.
1 FLASH
2 FLASHES
3 FLASHE_
• Blown fuse or
circuit breaker.
• Integrated
control
module has an
internal fault.
• Furnace lockout due
to an excessive
number of ignition
attempts. (3 total) _
• Auxiliary
Limit Open
• Pressure
switch
circuit is closed.
• Induced draft
blower
is not
operating.
• Pressure
switch
circuit not closed.
• Induced draft
blower
is operating.
• Blown fuse or circuit
breaker.
• Integrated
controi module
has an internal fault.
• Failure to establish
flame.
Cause may be no gas to
burners, bad igniter or
igniter alignment, improper
orifices,
or coated/
oxidized or improperly
connected
flame sensor.
• Loss of flame after
establishment.
Cause may
be interrupted
gas supply,
lazy burner flames
(improper
gas pressure
or restriction
in flue or
improper
induced draft
blower
performance.
• Insufficient
conditioned
air
over the heat exchanger.
Blocked filters, restrictive
ductwork,
improper
circulator
blower
speed,
or failed circulator
blower.
• Induced
draft blower
pressure
switch
contacts
sticking.
• Shorts
in pressure
switch
circuit.
• Pressure
switch
hose
blocked,
pinched or
connected
improperly.
• Blocked flue or weak
induced
draft blower.
• Incorrect
pressure
switch
setpoint
or malfunctioning
switch
contacts.
• Loose or improperly
connected
wiring.
• Assure 115 and 24 volt
power
to furnace
integrated
control
module.
• Check integrated
control
module fuse (3A).
Replace if necessary.
Check for possible
shorts in 115 and 24 volt
circuits.
Repair as
necessary.
• Replace bad integrated
control module.
• Locate and correct
gas interruption.
• Replace or realign
igniter.
• Check flame sense
signal. Sand sensor
if coated and/or
oxidized.
• Check flue piping for
blockage,
proper
length, elbows, and
termination.
• Verify proper
induced
draft blower
performance.
• Check circulator
blower
speed and
performance.
Correct speed or
replace
blower
if
necessary.
• Replace induced
draft blower
pressure
switch.
• Repair short.
• Inspect
pressure
switch
hose. Repair,
if necessary,
• Inspect flue for
blockage,
proper
length, elbows, and
termination.
• Correct
pressure
switch
setpoint
or
contact
motion.
• Tighten or correct
wiring
connection.
• Turn power OFF
prior to repair.
Replace integrated
control module
fuse with 3A
automotive
fuse.
• Turn power OFF
prior to repair.
• Read precautions
in "Electrostatic
Discharge"
section
of manual.
• Turn power OFF
prior to repair.
• Igniter is fragile,
handle with care.
• Clean flame
sensor with steel
wool.
• See "Combustion
and Ventilation Air
Requirements"
and
"Category I
Venting
(Vertical
Venting)"
section
for details.
• See Product Data
Bulletin for
allowable
rise
range and proper
circulator
speed.
Turn power OFF
prior to repair.
Replace
pressure
switch
with
proper
replacement
part.
• Turn power OFF
prior to repair.
• See "Combustion
and Ventilation
Air
Requirements"
and "Category I
Venting
(Vertical
Venting)"
section
for details.
• Replace
pressure
switch
with proper
replacement
part.
1Integrated control module will automatically
attempt to reset from lockout after one hour.
2 LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
29