Vent Guidelines: Exhaust
This water heater must be vented/terminated vertically to the outside of the building or
structure. This water heater is NOT designed or certified for side wall horizontal vent
terminations.
All installations must be vented in accordance with the National Fuel Gas Code NFPA 54/ANSI
Z223.1 – latest edition and the requirements of State or local codes. In Canada, the furnaces
must be vented in accordance with National Standard of Canada, CAN/CSA B149.2 – latest
editions and amendments and the codes of the local utility or other authority having
jurisdiction.
NOTE: The vertical height of the Category I venting system must be at least as great as the
horizontal length of the venting system.
• All vent (Category I) passing through a concealed space, an attic or floor, MUST be Type B
double wall vent and/or Type B double wall vent connectors. For vent passing through an
internal wall, use Type B with ventilated thimble ONLY.
• The RH180 CANNOT be vented into any chimney serving an open fireplace or any other solid
fuel burning appliance.
• Use the same diameter Category I connector or vent as permitted by NFPA 54/ANSI z223.1
venting tables.