2: Ademco Contact Id Format Event Code Description - Fire-Lite Alarms Fire-Watch 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Central Station Communications
4.0.2 Ademco Contact ID Format Event Code Description
This section describes the various Event Codes and their messages which are available for the Ademco Contact ID
Format. The reporting structure for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC
Where:
SSSS
= Four digit Subscriber ID Account Code (addresses 21 - 24 and 51 - 54)
18
= Identifies transmission as Contact ID to the receiver at the Central Station
Q
= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ
= Event code (shown in Tables)
GG
= Group number
CCC
= Channel/Input number
Notes:
18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
1.
alarm and trouble report.
Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or
2.
R for New Restore.
GG Group Number is fixed at '00' and cannot be changed.
3.
CCC Channel/Input Number is transmitted as '001' for Channel/Input 1, '002' for Channel/Input 2, '003' for
4.
Channel/Input 3, '004' for Channel/Input 4.
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the
Ademco Contact ID Reporting Structure follows:
Time
Date
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
56
Rcvr/Line ID
SSSS
QXYZ
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
GG
CCCC
E110
00
C001 - general fire alarm on Channel/Input 1
E111
00
C002 - smoke detector alarm on Channel/Input 2
E380
00
C003 - fault on Channel/Input 3
R110
00
C001 - Channel/Input 1 alarm restored
R111
00
C002 - smoke detector Channel/Input 2 restored
R380
00
C003 - Channel/Input 3 fault restored
E158
00
C004 - high temperature, Channel/Input 4
E151
00
C004 - gas detected, Channel/Input 4
Document #51073
Rev.A
1/19/99
P/N 51073:A