Advertisement

5.4 — Remove From Service
To ensure safety, follow the steps below prior to inspection, maintenance or service.
IMPORTANT NOTE: If currently experiencing a utility outage, see Subsection 6.3 —Removal From Service
During Utility Outages for special instructions.
Open the viewing window. See Subsection 3.5 —Open Viewing Window.
1.
Move the Main Circuit Breaker switch down to the OFF (Open) position. See A of Figure 5-6.
2.
Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode. See B of
3.
Figure 5-6.
Remove T1 fuse from transfer switch.
4.
Pull up rubber flap covering fuse holder and remove 7.5 amp fuse. See C of Figure 5-6.
5.
Place a DO NOT OPERATE tag or placard on both the control panel and transfer switch.
6.
If the unit has been running, wait five minutes for the engine to cool.
7.
A
Main Circuit Breaker
5.5 — 30 Hour Break-In
Perform the following task:
Replace Lubricating Oil and Oil Filter
NOTE: See Subsection 5.8.1 under Schedule B Maintenance.
5.6 — Daily Maintenance (If Running Continuously)
Perform the following tasks:
Check Fuel Level and Fill
Drain Fuel Filter
Check Fuel Lines and Hoses
Check Coolant Level
NOTE: See Subsection 5.7.1 through Subsection 5.7.6 under Schedule A Maintenance.
Owner's Manual for Stationary Diesel Generators
LCD Screen
o
OFF
PUSH TO TRIP
Control Pad
Figure 5-6. Generator Control Panel
7.5 Amp Fuse
and USB Port
Check Coolant Hoses
Check Radiator for Clogging
Check Lubricating Oil Level
Maintenance
C
B
31