Alarm/Warning Conditions; Change Time And Date; Programmable Timers; Dealer Programmable - Generac Power Systems RD015 Owner's Manual

Power series
Hide thumbs Also See for RD015:
Table of Contents

Advertisement

Operation
4.4 — Alarm/Warning Conditions
The owner/operator is alerted to Alarm and/or Warning conditions via the control panel LCD screen. All Alarm condi-
tions cause the generator to shut down. The Warning messages alert the operator to conditions that do not disable the
unit or require immediate correction.
The possible Alarm/Warning messages are listed below.
Alarm Messages
High Engine Temperature
Low Oil Pressure
Overcrank
Overspeed
RPM Sense Loss
Underspeed
Controller Fault
Ignition Fault Code
WIRING ERROR
Over Voltage
Under Voltage
Overload Remove Load
Canbus Error
Governor Fault
Missing Cam Pulse
Missing Crank Pulse
Ruptured Tank
Low Fuel (10%)
E-Stop
Fuse Problem
NOTE: Unless properly trained to correct and clear Alarm/Warning conditions, contact an Authorized Dealer or trained
service technician.
4.5 — Change Time and Date
To change the time and date after activation, see the Navigation Menu in Figure 4-3. If power is lost (battery is discon-
nected/reconnected, control panel fuse is removed/installed, etc.), the display automatically prompts the user for the
Time and Date. All other information is retained in memory.
4.6 — Programmable Timers
4.6.1— Dealer Programmable
4.6.1.1—Exercise Time
A programmable exercise time is provided. In the AUTO mode, the engine starts and runs once each week at the time
and day specified. During the exercise cycle, the unit runs approximately 12 minutes and then shuts down. Transfer of
loads to the generator does not occur unless utility power fails.
NOTE: A Dealer password is required to change the Exercise time.
22
Warning Messages
Low Battery
Exercise Set Error
FIRMWARE ERROR-9
Schedule A Maintenance
Schedule B Maintenance
Schedule C Maintenance
Battery Problem
Charger Warning
Charger Missing AC
Overload Warning
Overload Cooldown
SEEPROM ABUSE
USB Warning
Download Failure
Low Fuel (20%)
Stopping...
Owner's Manual for Stationary Diesel Generators

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd030Rd020Rd048Rd0500066781

Table of Contents