ABB ACS350 User Manual page 236

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

236
Parameters – complete descriptions
Index Name/Selection
SPV1UNDORDLY
SPV2UNDORDLY
SPV3UNDORDLY
CNTR OVER
CNTR UNDER
LOGIC VAL
ENTER SETPNT
AT SETPOINT
AI1 L1 & DI5
AI2 L2 & DI5
AI1 H1 & DI5
AI2 H2 & DI5
AI1 L1 & DI4
AI2 L2 & DI4
AI1 H1 & DI4
AI2 H2 & DI4
DLY AND DI1
DLY AND DI2
DLY AND DI3
DLY AND DI4
DLY AND DI5
DLY & AI2 H2
DLY & AI2 L2
DLY & AI1 H1
DLY & AI1 L1
Actual signals and parameters
Description
See selection SPV1OVRORDLY.
See selection SPV2OVRORDLY.
See selection SPV3UNDORDLY.
State change when counter value exceeds the limit defined by par.
COUNTER LIMIT. See parameters 1904...1911.
State change when counter value is below the limit defined by par.
COUNTER LIMIT. See parameters 1904...1911.
State change according to logic operation defined by parameters
State change when drive output frequency/speed enters the reference area
(i.e the difference is less than or equal to 4% of the maximum reference).
State change when drive output frequency/speed equals the reference value
(= is within tolerance limits i.e the error is less than or equal to 1% of the
maximum reference).
State change when AI1 value < par.
DI5 is active.
State change when AI1 value < par.
DI5 is active.
State change when AI1 value > par.
DI5 is active.
State change when AI1 value > par.
DI5 is active.
State change when AI1 value < par.
DI4 is active.
State change when AI1 value < par.
DI4 is active.
State change when AI1 value > par.
DI4 is active.
State change when AI1 value > par.
DI4 is active.
State change when delay time defined by parameter
DLY has elapsed and DI1 is active.
State change when delay time defined by parameter
DLY has elapsed and DI2 is active.
State change when delay time defined by parameter
DLY has elapsed and DI3 is active.
State change when delay time defined by parameter
DLY has elapsed and DI4 is active.
State change when delay time defined by parameter
DLY has elapsed and DI5 is active.
State change when delay time defined by parameter
DLY has elapsed and AI2 value > par.
State change when delay time defined by parameter
DLY has elapsed and AI2 value < par.
State change when delay time defined by parameter
DLY has elapsed and AI1 value > par.
State change when delay time defined by parameter
DLY has elapsed and AI1 value < par.
8412
SEQ VAL 1 LOW value and when
8414
SEQ VAL 2 LOW value and when
8411
SEQ VAL 1 HIGH value and when
8413
SEQ VAL 2 HIGH value and when
8412
SEQ VAL 1 LOW value and when
8414
SEQ VAL 2 LOW value and when
8411
SEQ VAL 1 HIGH value and when
8413
SEQ VAL 2 HIGH value and when
8424
ST1 CHANGE
8424
ST1 CHANGE
8424
ST1 CHANGE
8424
ST1 CHANGE
8424
ST1 CHANGE
8424
ST1 CHANGE
8413
SEQ VAL 2 HIGH value.
8424
ST1 CHANGE
8414
SEQ VAL 2 LOW value.
8424
ST1 CHANGE
8411
SEQ VAL 1 HIGH value.
8424
ST1 CHANGE
8412
SEQ VAL 1 LOW value.
Def, FbEq
45
46
47
1905
48
1905
49
8406...8410
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69