74 OVERHEAT LOCKOUT - 1 FILL SYSTEM TO 1.0 BAR - 2 BLEED RADIATORS -
3 CHECK RADIATOR VALVES OPEN -
Is the Boiler and CH System filled with water and all
isolation and radiator valves open?
Is the Flow/Return Differential across the Boiler in
excess of 30°C?
Check the Flow and Return Thermistors
(Refer to Frame 69)
Check resistance using a suitable multimeter
connected across the thermistor's terminal pins
o
At 25
C
expect
o
At 60
C
expect
At 85
o
C
expect
ReStARt PRoCedURe - To restart boiler, turn mode knob to restart position and immediately turn knob back to required setting.
75 iGnition loCKoUt - 1 CHeCK otHeR GAS APPliAnCeS WoRK -
2 ReStARt boileR - 3 ContACt inStAlleR
If the boiler is restarted does the
boiler ignite for a short time and
then extinguish?
YES
Check the detection electrode
and associated harness for:
continuity, visual condition and
position (Refer to Frame 51).
Check if the condensate pipe is
blocked.
Replace as necessary
Check siphon and condensate
drain pipe work for blockage and
rectify if necessary. Boiler now
working OK?
NO
Replace Gas Valve
* note: due to the wave form of the rectified voltage, the reading will vary depending on the type of meter used to measure the
value. In general terms a reading greater than 150V indicates that the correct voltage is supplied to the gas valve.
ReStARt PRoCedURe - To restart boiler, turn mode knob to restart position and immediately turn knob back to required setting.
+
Ideal Logic
Combi -
Fault Finding
YES
NO
9,700 - 10,300
Ohms
2,400 - 2,600
Ohms
1,000 - 1,100
Ohms
NO
Is the Gas Pressure available at
the Boiler Inlet (>18 mbar)?
Is approx 215Vdc supply available
at the Gas Valve? (* See note)
Unplug gas valve. Is resistance
between outside pins between
4k Ω (± 2)?
Check spark generator and
associated harness for: continuity
and visual condition. (Refer to
Frame 52) Are these functioning
correctly?
YES
Check ignition electrode and
associated harness for: continuity,
visual condition and position.
(Refer to Frame 50) Are these
functioning correctly?
Installation and Servicing
4 RESTART BOILER - 5 CONTACT INSTALLER
NO
Fill and vent the system and open all
isolation valves, then restart boiler
Check that the Pump is rotating freely. Is
YES
the Differential now below 20°C?
NO
Replace the Pump,
then restart boiler
YES
YES
YES
YES
YES
OK, now
restart boiler
NO
Check gas supply and
rectify fault
Check wiring connection
NO
from gas valve to PCB for
continuity. If the wiring is
OK then replace the PCB
NO
Replace Gas Valve
NO
Replace Spark
Generator and harness
as necessary
Replace Ignition
NO
Electrode and
associated harness as
necessary