Tools Required - Lennox Elite Series Installation Instructions Manual

Table of Contents

Advertisement

Check
the
condensate
drain
line for
free
and
unobstructed flow; clean, if necessary
Adjust blower speed for cooling Measure the pressure
drop over the coil to determine the correct blower CFM
Refer to the unit information service manual for pressure
drop tables and procedure
Check drive belt for wear and proper tension
NOTE - if owner reports insufficient cooling, the unit
should be gauged and refrigerant charge checked
Refer
to
section
on
refrigerant charging
in
this
instruction
IMPORTANT
Use this check-out procedure (see checklist immediately
following)
to
verify
part-load
and
full-load
capacity
operation of two-stage modulation compressors
TOOLS REQUIRED
Refrigeration gauge set
Digital volt/amp meter
Electronic temperature thermometer
On-off toggle switch
PROCEDURE
NOTE - Block outdoor coil to maintain a minimum of 375
psig during testing)
1 Turn main power OFF to outdoor unit
2 Adjust room thermostat set point 5°F above the room
temperature
3 Remove
control access panel
Install refrigeration
gauges on unit Attach the amp meter to the common
(black wire) wire of the compressor harness Attach
thermometer to discharge line as close as possible to
the compressor
4 Turn toggle switch OFF and install switch in series with
Y2 wire from room thermostat
5 Cycle main power ON
6 Allow pressures and temperatures to stabilize before
taking measurements
(may take up to 10 minutes)
7 Record all of the readings for the Y1 demand
8 Close switch to energize Y2 demand
Verify power is
going to compressor solenoid
9 Allow pressures and temperatures to stabilize before
taking measurements
(may take up to 10 minutes)
10 Record all of the readings with the Y1 and Y2 demand
11 If temperatures and pressures change in the direction
noted in chart, the compressor is properly modulating
from low to high capacity (If no amperage, pressures
or temperature
readings
change when this test is
performed, the compressor is not modulating between
low and high capacity and replacement is necessary)
12 After testing is complete, return unit to original set up
In order to ensure peak performance, your system must be
properly maintained
Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level
1 Air Filter--Ask
your Lennox dealer to show you where
your indoor unit's filter is located It will be either at the
indoor unit (installed internal or external to the cabinet)
or behind a return air grille in the wall or ceiling Check
the filter monthly and clean or replace it as needed
2 Disposable
Filter--Disposable
filters
should
be
replaced with a filter of the same type and size
NOTE - If you are unsure about the filter required for
your system, call your Lennox dealer for assistance
,& IMPORTANT
3 Reusable
Filter--Many
indoor units are equipped
with reusable foam filters
Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille
NOTE - The filter and all access panels must be in
place any time the unit is in operation
4, Electronic
Air
Cleaner--Some
systems
are
equipped with an electronic air cleaner, designed to
remove airborne particles from the air passing through
the cleaner. If your system is so equipped, ask your
dealer for maintenance
instructions,
5, Indoor
Unit--The
indoor unit's evaporator
coil is
equipped with a drain pan to collect
condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed,)
IMPORTANT
6 Outdoor
Unit--Make
sure no obstructions
restrict
airflow to the outdoor unit Leaves, trash or shrubs
crowding the unit cause the outdoor unit to work harder
Page 26
505329M
04/08

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp16 series

Table of Contents