The 5-strike pressure switch lockout condition can be reset
by cycling OFF the 24-volt power to the control board or by
shorting the TEST pins between 1 to 2 seconds. All timer
functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is
engaged, a 5-minute short cycle will occur after the switch
closes.
DEFROST SYSTEM SENSORS
Sensors
connect
to
the
defrost
board
through
a
field-replaceable
harness assembly that plugs into the
board as illustrated in figure 39 on page 23. Through the
sensors, the board detects outdoor ambient, coil, and
discharge temperature fault conditions. As the detected
temperature changes, the resistance across the sensor
changes. Sensor resistance values can be checked by
ohming across pins shown in table 11.
Table 11. Sensor Temperature/Resistance
Range
Pins/W
Temperature
Resistance values
ire
Sensor
Range °F (°C)
range (ohms)
Color
Outdoor
-35 (-37) to 120 (48)
280,000 to 3750
3 & 4
(Black)
Coil
-35 (-37) to 120 (48)
280,000 to 3750
5 & 6
(Brown)
Discharge (if
24 (-4) to 350 (176)
41,000 to 103
1 & 2
applicable)
(Yellow)
Note: Sensor resistance increases as sensed temperature decreases.
Figure
37 shows
how the resistance
varies as the
temperature changes for both type of sensors.
NOTE - When checking the ohms across a sensor, be
aware that a sensor showing a resistance value that is not
within the range shown in table 11, maybe performing as
designed. However, if a shorted or open circuit is detected,
then the sensor may be faulty and the sensor harness will
need to be replaced.
1
ml157_O
I
mMm7450
19275
11775
B
15425
_
19975
26200
[]
34375
mm46275
I
62700
85300
i
10000
30000
50000
70000
90000
RESISTANCE
(OHMS)
Figure 37. Temperature/Resistance
Chart
(Ambient and Coil Sensors)
m
m250
roll
m325
m
m425
m
m600
m
m825
m1175
WOO
_025
"500
3000
3750
4650
5825
1000
2000
3000
4000
5000
6000
RESISTANCE
(OHMS)
Figure 38. Temperature/Resistance
Chart
(Discharge
Sensor)
Ambient
Sensor--The
ambient
sensor
considers
outdoor temperatures below -35°F (-37°C) or above 120°F
(48°C) as a fault. If the ambient sensor is detected as being
open, shorted or out of the temperature
range of the
sensor,
the board will
not perform
demand
defrost
operation.
The board will revert to time/temperature
defrost operation and will display the appropriate
fault
code. Heating and cooling operation will be allowed in this
fault condition.
Coil
Sensor--The
coil temperature
sensor considers
outdoor temperatures below -35°F (-37°C) or above 120°F
(48°C) as a fault. If the coil temperature sensor is detected
as being open, shorted or out of the temperature range of
the sensor,
the board will
not perform
demand
or
time/temperature
defrost operation and will display the
appropriate fault code. Heating and cooling operation will
be allowed in this fault condition.
Discharge
Line
Sensor--If
the
discharge
line
temperature
exceeds
a temperature
of 300°F (148°C)
during compressor operation, the board will de-energize
the compressor contactor output (and the defrost output, if
active). The compressor will remain off until the discharge
temperature
has dropped below 225°F (107°C) and the
5-minute anti-short cycle delay has been satisfied. This
sensor has two fault and lockout codes:
.
,
If the board recognizes
five high discharge
line
temperature
faults during a single (Y1) compressor
demand, it reverts to a lockout mode and displays the
appropriate code. This code detects shorted sensor or
high discharge
temperatures.
(Code
on board is
"Discharge Line Temperature Fault and Lockout").
If the board recognizes five temperature sensor range
faults during a single (Y1) compressor
demand, it
reverts to a lockout mode and displays the appropriate
code.
The
board
detects
open
sensor
or
out-of-temperature
sensor
range.
This
fault
is
detected by allowing the unit to run for 90 seconds
before
checking
sensor
resistance.
If the sensor
resistance is not within range after 90 seconds, the
board will count one fault. After five faults, the board
will lockout. (Code on board is "Discharge Sensor
Fault and Lockout").
505329M
04/08
Page 22