Monitor kit
Two-stage Lennox room thermostat
!!!
!!!!!!!!!!!!!!!!!!
Expected results during Y2
Unit Readings
Y1 - First-Stage
demand (Toggle switch On)
Y2 - Second-Stage
COMPRESSOR
Voltage
Same
Amperage
Higher
OUTDOOR UNIT FAN
MOTOR
Amperage
Same or Higher
TEMPERATURE
Ambient
Same
Outdoor Coil Discharge Air
Higher
Compressor Discharge Line
Higher
Indoor Return Air
Same
Indoor Coil Discharge Air
Lower
PRESSURES
Suction (Vapor)
Lower
Liquid
Higher
Customer
Address
Indoor Unit Model
Serial
Outdoor Unit Model
Serial
Notes:
START UP CHECKS
Refrigerant Type:
1st Stage: Rated Load Amps
2nd Stage: Rated Load Amps
Outdoor Unit Fan Full Load Amps
COOLING
MODE
Suction
Pressure:
1st Stage:
Liquid Pressure:
1st Stage:
Supply Air Temperature:
1st Stage:
Temperature:
Ambient:
Actual Amps
Rated Volts
Actual Volts
Actual Amps
Rated Volts
Actual Volts
Actual Amps:
1st Stage
2nd Stage
2nd Stage:
2nd Stage:
2nd Stage:
Return Air:
System Refrigerant Charge (Refer to manufacturer's
information on unit or installation instructions for required sub-
cooling and approach temperatures,)
Subcooling:
A
B
SUBCOOLING
Saturated Condensing Temperature (A)
--
=
minus Liquid Line Temperature (B)
Approach:
A
B
APPROACH
Liquid Line Temperature (A) minus
--
=
Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
A
B
COIL TEMP DROP
Return Air Temperature (A) minus
--
=
Supply Air Temperature (B)
Page 28