Lennox Elite Series Installation Instructions Manual page 19

Table of Contents

Advertisement

8UBCOOLING
2
USE COOLING
MODE
60°F (15 °) --
USE HEATING
MODE
Check the airflow as illustrated in figure 32 to be sure the indoor airflow is as required.
(Make any air flow adjustments before continuing with the following procedure0
Measure outdoor ambient temperature; determine whether to use cooling
mode or
heating mode to check charge.
3
Connect gauge set.
4
Check liquid and vapor line pressures. Compare pressures with either heat or cooling mode
normal operating pressures in tables 8 and 9 (second stage - high capacity),
NOTE - The reference table is a general guide. Expect m#nor pressure variations.
Significant
differences may mean improper charge or other system problem.
5
Set thermostat for heat/cool demand, depending on mode being used:
Using cooling
mode--When
the outdoor ambient temperature
is 60°F (15°C) and above.
Target subcooling values (second stage - high capacity) in table 8 are based on 70 to 80°F
(21-27°C)
indoor
return air temperature;
if necessary,
operate
heating to reach that
temperature range; then set thermostat to cooling mode setpoint to 68°F (20°C) which should
call for second stage (high capacity) cooling. When pressures have stabilized, continue with
step 6.
%
SAT o
LIQ o -
SC o
=
Using heating mode--When
the outdoor ambient temperature is below 60°F (15°C). Target
subcooling values (second stage - high capacity) in table 9 are based on 65-75°F (18-24°C)
indoor return air temperature;
if necessary, operate cooling to reach that temperature
range;
then set thermostat to heating mode setpoint to 77°F (25°C) which should call for second stage
(high capacity) heating. When pressures have stabilized, continue with step 6.
6
Read the liquid line temperature;
record in the LIQ ° space.
7
Read the liquid line pressure; then find its corresponding
temperature
in the temperature/
pressure chart listed in table 10 and record it in the SAT ° space.
8
Subtract LIQ ° temp. from SAT ° temp. to determine subcooling; record it in SC ° space.
9
Compare SC ° results with table below, being sure to note any additional charge for line set
and/or match-up.
10 If subcooling value is greater than shown in tables 4 through 7 for the applicable unit, remove
refrigerant; if less than shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 4 through 10 to verify charge.
Figure 34. Using Subcooling Method -- Second Stage (High Capacity)
Table 4. XP16-024
Target
INDOOR
HEAT
Subcooling
**Add
MATCHUP
PUMP
Heat Cool
charge
(+5°F) (+I°F)
CBX26UH-018
20
8
1
5
CBX26UH-024
20
8
1
5
CB27UH-024
12
6
O
12
CB27UH-030
13
9
1
12
CB3OU
21/26
12
6
O
12
CB3OU
31
13
9
1
12
CBX32M-018/024
12
6
O
12
CBX32M-030
13
9
1
12
CBX32MV
024/030
13
9
1
12
CBX32MV
036
12
9
O
10
CH33-25B
17
4
O
O
CH33-36A-2F
12
6
O
10
CH3_36B_F
17
4
O
O
CH33
36C 2F
12
7
1
2
CR33-24A/B-F
20
4
O
O
CR33-3O/36A/B/C-F
20
8
1
6
CR33
48
21
9
O
3
CX34_5A/_6F
12
6
O
12
CX34-31A/B-6F
20
9
1
12
CX34-36A/B/C-6F
17
5
O
5
CX34
38A/B
6F SerialNo#before6007K
31
7
O
8
CX34_8A/_6F
SerialNo#6007K andafter
10
8
O
11
CX34-19
18
4
O
1
Table 5. XP16-036
Target
INDOOR
HEAT
Subcooling
**Add
MATCHUP
PUMP
Heat
Cool
charge
(*5°F) (*I°F)
ililili'11"
.....
CH23_1
17
7
O
13
CH23-65
12
8
1
10
CBX26UHq330
25
8
1
14
CBX26UH
036
25
8
1
14
CB27UH-036
17
8
2
4
CB27UH-042
17
8
2
4
CB3OU_I
17
6
O
O
CB3OU-41/46
17
8
2
4
CBX32M-030
17
6
O
O
CBX32M-036
17
8
2
4
CBX32MV-024/030
17
6
O
O
CBX32MV
036
17
8
2
4
C33 44C
17
8
1
14
CH33-42B-2F
17
7
O
13
CH33_44/48_2F
12
8
1
8
CH33_48C_F
10
8
1
6
CH33-43B
9
10
1
6
CH33_49C
9
10
1
6
CR33_48B/C_
25
8
2
O
CR33-50/60C-F
25
9
0
14
CX34
38A/B_F
se.al No#before6007K
31
7
1
5
CX34
38A/B
6FSet_alNo#6OOTKandafter
10
8
1
12
CX34-43B/C-6F
10
8
1
6
CX34
6OD
9
9
O
14
**Amount
of charge required in additional to charge shown on unit nameplate.
(Remember
to consider Iine set length difference.)
Page 19
XP16 SERIES

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp16 series

Table of Contents