WARNING
during calibration, the three-way valve is switched to the heating circuit. If it is not possible to calibrate the gas valve
because the boiler turns off due to overtemperature, proceed as follows:
-
exit the calibration function;
-
make a DHW demand at maximum flow;
-
calibrate the gas valve to maximum power, as described in section 22.
To calibrate the gas valve at minimum power, activate the calibration function, as described in this section.
TABLE 1: CO2 COMBUSTION AND GAS NOZZLE
HT 330 - HT 1.280
max. CO
heat capacity
2
min. CO
heat capacity
2
CO max
Gas nozzle
Table 1a
HT 1.240 - HT 240 - HT 280
max. CO
heat capacity
2
min. CO
heat capacity
2
CO max
Gas nozzle
Table 1b
HT 1.120
max. CO
heat capacity
2
min. CO
heat capacity
2
CO max
Gas nozzle
Table 1c
INSTRUCTIONS FOR FITTERS
G20 - 2H - 20 mbar
8,7%
8,4%
< 250 ppm
12,0 mm
G20 - 2H - 20 mbar
8,7%
8,4%
< 250 ppm
7,5 mm
G20 - 2H - 20 mbar
8,7%
8,4%
< 250 ppm
4,0 mm
72
G31 - 3P - 37 mbar
10%
9,8%
< 250 ppm
12,0 mm
G31 - 3P - 37 mbar
10%
9,5%
< 250 ppm
7,5 mm
G31 - 3P - 37 mbar
10%
9,5%
< 250 ppm
4,0 mm
926.420.3 - EN