Baxi LINA 3 COMFORT HT Instruction Manual page 63

Condensing gas wall-hung boilers
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 44
15.4 SEPARATE HORIZONTAL FLUE TERMINALS INSTALLATION OPTIONS
IMPORTANT -
Make sure there is a minimum downward slope of 1 cm per metre of duct towards the boiler. Make
sure the flue and air ducts are firmly fixed to the wall with suitable brackets.
If fitting a single flue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the duct passes through
building walls. For detailed installation instructions, consult the technical data provided with the accessories.
15.5 SEPARATE VERTICAL FLUE TERMINALS INSTALLATION OPTIONS
INSTRUCTIONS FOR FITTERS
L max = 15 m
L max = 15 m
63
(L1 + L2) max = 80 m
The maximum length of the air duct
is 15 metres.
L max = 14 m
926.420.3 - EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents