Precautions for the following installation types:
C
, C
The terminals for separate flues must be fitted inside a 50 cm square.
13
33
Detailed instructions are provided with the individual accessories
C
Do not fit the flue and air duct terminals on opposite walls of the buil-
53
ding.
C
The pressure drop of the ducts must not exceed 100 Pa. The ducts
63
must be certified for this specific use and for a temperature in excess
of 100°C. The flue terminal must be certified EN 14471.
C
, C
The flue terminal or flue duct must be suitable for the purpose.
43
83
CAUTION
To optimise operating safety, make sure the flue ducts are firmly fixed to
the wall with suitable brackets.
... COAXIAL FLUE-AIR DUCT (CONCENTRIC)
This type of duct is used to discharge exhaust fumes and draw combustion
air both outside the building and if a LAS flue is fitted.
The 90° coaxial bend allows the boiler to be connected to a flue-air duct
in any direction as it can be rotated by 360°. It can also be used as a
supplementary bend combined with a coaxial duct or a 45° bend.
If fumes are discharged outside the building, the flue-air duct must
protrude at least 18mm from the wall to allow an aluminium weathering
surround to be fitted and sealed to avoid water infiltrations.
Make sure there is a minimum downward slope of 5 cm per metre of duct
towards the boiler.
A 90° bend reduces total duct length by 1 metre.
A 45° bend reduces total duct length by 0.5 metre
15.1 Ø 60/100 HORIZONTAL FLUE TERMINAL INSTALLATION OPTIONS
INSTRUCTIONS FOR FITTERS
L max = 10 m Ø 60/100 mm
L max = 25 m Ø 80/125 mm
L max = 9 m
Ø 60/100 mm
L max = 24 m
Ø 80/125 mm
61
C
33
C
13
C
43
Figure 8
Concentric adaptor
C
33
C
13
C
C
53
83
926.420.3 - EN