Smoke match position.
d) If spillage persists, the flue is not functioning correctly and a fault exists. If, after
investigation the fault cannot be traced and rectified, the fire must be disconnected
from the gas supply and expert advice obtained.
e) If there is an extractor fan fitted anywhere in the vicinity of the appliance, the spillage
test should be repeated with the fan running on maximum and all interconnecting doors
open.
f)
After ensuring that the fire is safe to use it should be left on high position to fully warm
up. During this time a slight odour may be noticed, this is due to the "newness" of the
fire and will soon disappear.