User Notices - Toyotomi TGS-28FWCA Owner's Manual

Table of Contents

Advertisement

☆ When operating, the entire capacity of the cooperating indoor unit should be not larger than
that of outdoor unit. Otherwise, it will cause the shortage of cooling (heating) capacity.
☆ A Breaker(or fuse) need to be installed in every indoor unit, and the capacity should in
according with indoor unit's electrical parameter; all the indoor units are required to be
centralized controlled by a total Switch, this Switch can cut off the electric power supply in
case of emergency. The Breaker(or fuse) on each indoor units have the function of short circuit
prevention and abnormal overload avoiding, it should be connected in normal situation. The
total switch controlling the power supply of all the indoor units. Before clearing and
maintenance job being carried out to the indoor units, it is very important to turn off the total
power supply switch.
In order to turn on the units successfully, the main power switch should be opened 8 hours before the
operation.
After receiving the turn off signal, every indoor unit will continue to work for 20-70sec to make use of the
rest cool air or the rest heat air in the heat exchanger, while preparing for the next operation. And this is
normal.
When the selected operating mode of the indoor unit are clash with the operating mode of the outdoor unit,
the malfunction light will blink after 5s on the indoor unit or remote controller showing that the operation
clash, then the indoor unit will stop. At this time, change the operation mode of the indoor unit to the one
that would not clash with the outdoor operating mode to make the operation normal. The cooling mode is
not clash with the dry mode, while the fan mode is not clash with any mode.
☆ The appliance shall not be installed in the laundry
☆ An all-pole disconnection switch having a contact separation of at least 3mm in all poles should
be connected in fixed wiring
☆ Missing information regarding electric supply tolerances(+/-10%, +/-1Hz) in documentation
☆ Missing information regarding humidity (30-95%) in documentation

USER NOTICES