Install the cassette type indoor unit
1-1.5m
×
(Correct) 1/100 or more gradient
(wrong)
☆ Use the drain hose and clamp attached. Insert the drain
Sponge(attachment)
hose to the drain vent, and then tighten the clamp.
Clamp
Clamp(attachment)
☆ Entwine the big sponge on the clamp of drain hose to
insulate heat.
Heat insulation should be done to indoor drain hose.
Drain step up pipe note
Drain hose
Sponge (gray)
Below 4mm
☆ The install height of the drain raising pipe should less
than 280mm.
☆ The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm.
Roof
Hoisting stand
Within 300mm
1-1.5m
below 280mm
Drain hose
Drain raising
hose
220mm
Clamp(attachment)
Ceiling
Instruction
☆ The slant gradient of the attached drain hose should be within
75mm so that the drain hole doesn't has to endure the unnecessary
D ra in h o s e (a tta c h m e n t)
outside force.
☆ Please install the drain hose according to the following process
if several drain hoses join together.
T-tie in join drain hose
Above100mm
The specs of the selected join drain hose should fits the running capacity of the unit.