Power Source

The iBB-N15 <and iBB-N15-M> provides a linecord for connection to
a 15 Amp 115VAC service. The total maximum current load for all
outlets on the iBB-N15 cannot exceed 12 Amps.
The iBB-2N15<-M> provides two linecords for connection to 15 Amp
115VAC services. The total maximum current load for outlets on any
linecord cannot exceed 12 Amps. Each linecord distributes power to
four outlets.
The iBB-N20<-M> provides a linecord for connection to a 20 Amp
115VAC service. The total maximum current load for all outlets on the
iBB-N20 cannot exceed 16 Amps.
The iBB-2N20<-M> provides two linecords for connection to 20 Amp
115VAC services. The total maximum current load for outlets on any
linecord cannot exceed 16 Amps. Each linecord distributes power to
four outlets.
The iBB-C10<-M> is for international applications and can be used
on 100V to 240VAC. The iBB-C10 provides an IEC 320 style universal
inlet for connecting a detachable power cord. A standard IEC to CEE7
European cord set is supplied with the unit for use on 10 Amp 240VAC
service*. The total maximum current load for all outlets cannot exceed
12 Amps at 115VAC or 10 Amps when used at 240VAC.
The iBB-2C10<-M> is for international applications and can be used
on 100V to 240VAC. The iBB-2C10 provides two IEC 320 style
universal inlets for connecting a detachable power cord. Two standard
IEC to CEE7 European cord sets are supplied with the unit for use on
10 Amp 240VAC service*. The total maximum current load for outlets
on any linecord cannot exceed 12 Amps at 115VAC or 10 Amps when
used at 240VAC. Each linecord distributes power to four outlets.
The iBB-C20<-M> is for international applications and can be used
on 100V to 240VAC. The iBB-C20 provides an IEC 320 style universal
inlet for connecting a detachable power cord. A standard IEC to CEE7
European cord set is supplied with the unit for use on 20 Amp 240VAC
service*. The total maximum current load for all outlets cannot exceed
16 Amps.
The iBB-2C20<-M> is for international applications and can be used
on 100V to 240VAC. The iBB-2C20 provides two IEC 320 style
universal inlets for connecting a detachable power cord. Two standard
IEC to CEE7 European cord sets are supplied with the unit for use on
16 Amp 240VAC service*. The total maximum current load for outlets
on any linecord cannot exceed 16 Amps. Each linecord distributes
power to four outlets.
* Power cords for other countries are available from your local source. If a power cord with a different terminating plug