Basic Operation; Web Interface - Dataprobe iBootBar iBB-N15 Installation And Operations

Hide thumbs Also See for iBootBar iBB-N15:
Table of Contents

Advertisement

Basic Operation

Web Interface

The iBootBar web interface provides the easiest means of operating the outlets and monitoring the current status of the
units. One or more outlets can be simultaneously
controlled with a few mouse clicks. In cluster
configurations, all 128 outlets can be managed
from the web pages.
The interface is divided into three sections Header,
Control, and Status.
Each user will only be able to view and control the
outlets, devices and groups that have been
assigned to the user.
Header The Header identifies the iBootBar currently being accessed. If multiple iBootBars are deployed in a cluster
configuration, this will be the master iBootBar.
The Header allows the selection of various Status Vviews. To select an individual iBootBar, or predefined group of
outlets, click on the one of the two dropdown lists. To select the global view, click on Global. To see the status of the
AutoPing feature, click on AutoPing.
Control The Control panel provides the clickable buttons to change status of one or more
outlets. Once one or more outlets have been selected, click on the On, Off, or Cycle button.
Cycle will perform a timed change in outlet state; either Reboot (On-Off-On), or Cycle (Off-On-
Off) depending on the current state of the outlet.
The Cycle timer box allows selection of the length, in seconds, of all cycle or reboot operations.
Entries of 1 to 99 seconds are valid.
The Delay timer box allows selection of the delay time, in seconds, between the turning on of
each outlet whenever more than one outlets are turned on from the same command. This can
be used to prevent over-current draw on initial power up of devices. Entries of 0 to 99 seconds
are valid.
The Select All and Select None buttons allow selection or de-selection of all outlets.
Refresh provides an update of the status page to display current conditions. Web pages are
static moments in time, so use the Refresh obtain the latest status.
Logout terminates the session.